11
3.0
FX-3500 Overview
This chapter lists all the possible components of an FX-3500 system.
3.1
FX-3500 Fire Alarm Control Panel Models
All FX-3500 Fire Alarm Control Panels have the following features:
•
Main Board, Power Supply and Backbox.
•
Multi-zone fire alarm control panel.
•
MAM-3500 Main Display with 4 x 20 LCD display.
•
Class A (Style 6), Class X (Style 7), or Class B (Style 4)
analog
loop(s).
•
Four Power Limited Class B (Style Y), Class A (Style Z) NAC circuits (max. 1.5 Amps
each - 6.0 Amps total).
•
Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
•
Additional RAX-1048TZDS Display Adder Module can be added to provide 96
annunciation points per Adder.
•
Additional outputs include connections for a RTI remote trouble indicator, PR-300
Reverse Polarity Module, an RS-485 bus for connection of up to seven RAX-LCD-LITE,
RAM-3500-LCDs, SRM-312s and RA-1000 Series annunciators.
•
Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC
filtered and regulated, and resettable auxiliary power supply.
Figure 1
FX-3500 with DOX-1024DSR
Summary of Contents for FX-3500
Page 2: ......