Communication line has to be twisted pair, we recommend to use readily available CAT5 or 
CAT6 cable. In case of longer connection (hundreds of meters), terminate both ends of 
communication line by 150 ohm resistor connected between ZA and ZB poles. Use unused 
wires in parallel for each power pole connection to minimize power drop, especially if you use 
power leads also for powering other device like preamplifier, antenna switch or similar device. 
For proper ARXC module functionality voltage at its power terminal should be at least 7V. 
Maximal consumption (including powered device) is 500mA limited internally by ARCO. It is 
ample power for ARXC devices alone, but if provided power reserve is not enough for powering 
controlled devices, use D-SENSOR output only for ARXC modules and power controlled 
devices using separate power supply.

ARXC MODULE

 D-SENSOR PORT NAME

 PIN NUMBER

ZA

ZA

2

ZB

ZB

1

+12V

+12 V OUT

10

GND

GND

9

For controlling external devices, ARXC.REL 
provides one SPDT contact per relay, 
allowing to connect and implement any kind 
of switching requirement. Contacts are 
located at a pluggable  terminal for simpler 
assembly. Each energized relay is indicated 
by LED indicator and each relay can be 
manually energized by related pushbutton to 
help in-field troubleshooting.

5

ARCO connection to single ARXC.REL

Summary of Contents for ARXC.LoRa

Page 1: ...microHAM 2022 All rights reserved ARXC ARCO External Control Accessories ARXC REL ARXC MAG ARXC LoRa microHAM www microham com microHAM s r o Maticna 28 92401 Galanta Slovakia v1 1 2022 1...

Page 2: ...Ra 3 2 ARXC HARDWARE SETUP 4 ARXC REL addressing 4 ARXC wiring 4 3 ARXC SOFTWARE SETUP 9 ARXC MAG Settings 9 Using ARXC MAG Sensor 10 ARXC REL Settings and Use 13 DECLARATION OF CONFORMITY 17 TRADEMAR...

Page 3: ...switches mast preamplifiers or anything what is suitable to be controlled from the ARCO user interface touch screen or VNC for Internet remote control ARCO uses preset buttons for relays control and...

Page 4: ...L module each module needs to have a unique address Address is set by combination of two DIP switches according to drawing on PC board next to DIP switch It is possible to set up to 4 different addres...

Page 5: ...l consumption including powered device is 500mA limited internally by ARCO It is ample power for ARXC devices alone but if provided power reserve is not enough for powering controlled devices use D SE...

Page 6: ...microHAM 2022 All rights reserved 6 ARCO connection to single ARXC REL and ARXC MAG ARCO connection to ARXC MAG...

Page 7: ...microHAM 2022 All rights reserved 7 ARCO connection to three ARXC REL and ARXC MAG...

Page 8: ...microHAM 2022 All rights reserved 8 Wireless ARCO connection to single ARXC REL and ARXC MAG using pair of ARXC LoRa...

Page 9: ...re continuously sampled and ARCO improves magnetic curve of the sensor ARXC MAG AZI Shows azimuth determined by ARXC MAG sensor SLIP CONTROL Enables or disables background checking if azimuth of main...

Page 10: ...licking on RESUME LEARNING button Note that disabling ARXC MAG at this point deletes the ARXC MAG calibration After transition to ACTIVE state it is recommended to store ARCO configuration to one of t...

Page 11: ...ck prerequisite Now in Menu Heading Calibration turn the rotator to at least 4 evenly spaced points by 90 i e North South East West and enter azimuth for these calibration points using CUSTOM button Y...

Page 12: ...ords LED is on if the general direction of terminal block of ARXC MAG is towards North Besides that LED indicates also presence or absence of communication from ARCO if ARCO communicates with ARXC MAG...

Page 13: ...n Menu System ARXCx In 1 of N there is always exactly one relay switched on This rule is enforced even when controlling relays in the ARXC Control window and in Menu System ARXCx Individual relays can...

Page 14: ...ditable name again used as reference to this group B one of applications of BCD N group is control of Four Square type of antenna arrays so if azimuth control is enabled for BCD N the primary directio...

Page 15: ...NTENNA 2 an ARXC group with the name 1OF3 1 is selected for ANTENNA 3 the pull down is opened and displays the list of available options If ARXC group is selected instead of ANTENNA x its name is give...

Page 16: ...nsequently in this window the individual or the common set of Presets is edited B exit from this window without changing the given Preset All other buttons in this window represent possible options to...

Page 17: ...orward backward buttons instead of individual relays control and in between them the current value or if azimuth control is enabled for given group the current primary direction is displayed DECLARATI...

Reviews:

Related manuals for ARXC.LoRa