37
Maintenance and service
ERR DETECTED!
MPPT OUTPUT
SHORT CIRCUIT
MPPT CHARGE DISABLED
10.5 Output Short Circuit
This error message will be displayed if the load being drawn
from the batteries is exceeding the amount of power that
the MPPT is capable of supplying.
If the load being drawn from the batteries is eg: 70A and you
only
have a 40A MPPT then this error will display on the MPPT.
If this error is detected, open up the MPPT and check the left ribbon cable and confirm that the ribbon
cable is securely fastened between the Display and the power card.
If the Ribbon Cable is secure then reduce the Load being drawn from the battery bank to clear the
error. (Restart the MPPT once the load has been reduced.)
11.
Maintenance and service
Caution
– Risk of Electric Shock.
Batteries may cause electric shock and have a high short-circuit current.
Please take the precautionary measures specified below and any other measures necessary
when working with batteries.
Remove wristwatches, rings and other metal objects.
Only use tools with insulated grips and handles.
Only authorized personnel should perform maintenance, inspection, and replacement
operations.
All wiring connections should be checked on a regular basis
PLEASE BE AWARE:
WARRANTY WILL BE NULL AND VOID IF PANEL
SURGE PROTECTION IS NOT INSTALLED WITH
ALL LCD MPPT INSTALLATIONS