34
EXTERNAL CONNECTIONS
EXTERNAL OUTPUT IS A
LOAD SHED DISCONNECT
press CHARGE to save
press DATA to change
LOAD RECONNECTING @
= 13.0V PER BAT PACK
press CHARGE to save
press DATA to change
LOAD DISCONNECTING @
= 11.0V PER BAT PACK
press CHARGE to save
press DATA to change
LOAD RECONNECTING @
= 13.0V PER BAT PACK
press CHARGE to save
press DATA to change
REMOTE BVT CONNECTED
VOLTAGE MPPT = xx.xV
BV= 0.00V ADJ- xx.xV
BT=25.0’C ADJ+ xx.xV
The following screen will appear:
9.3.2
Load Reconnect Voltage
If this is complete then the LOAD SHED RECONNECT voltage
can be programmed which can be between 12-14 volts per
pack:
➢
Press the
<DATA>
button to change the LOAD RECONNECT VOLTAGE
➢
Press the
<CHARGE> button
to save the setting
The
SOLAR ASSIST SIGNAL V2
switches the relay for 10 seconds when the battery voltage is
limiting the current into the system. This is when the
*
is flashing next to the Battery display.
If
SOLAR AST UPS CNTR1
is selected
(by pressing
<CHARGE>
to save).
The following screen will appear
:
The user can program the Voltage at which the RELAY
operates.
This is between 10-12 volts per pack, in 0.1 volt steps. If the
system is 48 volts multiply the settings by 4.
If this is complete then the
LOAD RELAY RECONNECT
voltage may be programmed which can be between 12-14 volts
per pack.
9.4
Battery Temp and Battery Voltage Sensor
When the sensor is plugged into the RJ12 connector then the
following screen will show:
This shows the battery temperature and voltage.
Should there be a problem with the cable or a poor connection
then the screen will flash ERROR.
Voltage MPPT shows the battery voltage at the output of the MPPT.
The BV shows the voltage at the battery terminals. The correction is shown as /-.
The Battery Temperature (BT) is then shown with the ADJ compensation.
If the Battery Voltage Temperature is disconnected, the MPPT will revert back to stand alone
readings.