Wiring the TPS or Discrete output version
Figure 3-2:
mA1+
HART
RS-485
PWR
TPS/DO
A
A
B
RS-485 A
RS-485 B
C
E
D
B
A
A
A
A. 24 VDC
B. R
load
(250 Ω
resistance)
C. HART-compatible host or controller; and/or signal device
D. R
load
(500
Ω
resistance recommended)
E. Signal converter/flow computer or discrete input device
Note
•
For operating the milliamp output with a 24V supply, a maximum total loop resistance of 657
Ω
is
allowed.
•
When operating the TPS or Discrete output with a 24 VDC power supply, a maximum total loop
resistance of 1300
Ω
is allowed.
CAUTION!
•
To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable
instrumentation cable to connect the meter. The instrumentation cable should have individual
screens, foil or braid over each twisted pair, and an overall screen to cover all cores. Where
permissible, connect the overall screen to earth at both ends (360° bonded at both ends).
Connect the inner individual screens at only the controller end.
•
Use metal cable glands where the cables enter the meter amplifier box. Fit unused cable ports
with metal blanking plugs.