Operation
optoNCDT ILR 102x/110x/115x
Interface parameter (RS422 menu)
Depending of the setting made in Serial Select the appropriate interface parameters are displayed or altered.
The following settings are possible:
-
RS422 (Factory setting):
Baud rate:
4.8 or 9.6 or 19.2 or 38.4 (Factory setting) or 57.6 kBaud
Data bit:
8 or 7 (Factory setting)
Stop bit:
2 or 1 (Factory setting), Parity: even
REPEAT or SINGLE:
REPEAT
(Factory setting) means that the sensor continuously sends measured
data via the serial interface without waiting for a request. In
SINGLE
mode, a string of measured data is
only supplied on request.
The RS422 interface is a reliable full duplex serial interface with a transfer rate up to 10 MBaud and a cable
length of 1,000 m. The screened connection cable is connected to the sensor connector and the ground
terminal of the control cabinet.
-
SSI:
1/10 = LSB = 0.1 mm (10 MIL) or
1/8 = LSB = 0.125 mm (8 MIL)
Codes:
BINÄR24, BINÄR25, GRAY24 or GRAY25 (Factory setting) are possible.
For a reliable data transfer the maximum clock speed depends on the cable length. The screened
connection cable is connected to the sensor connector and the ground terminal of the control cabinet.
Cable length /m
< 25
< 50
< 100
< 200
< 400
Clock speed
< 500 kHz
< 400 kHz
< 300 kHz
< 200 kHz
< 100 kHz
-
BUS-ADDR:
Address for external bus adapter. Here you can set for external bus adapter.
Operation mode
Parameter
Setup
Operation mode
SERIAL
>SSI
SERIAL
>EXT.BUS
SERIAL
>RS422
SERIAL
<RS422>
RS422
<ENTER>
SSI
<Gray25>
EXT.Bus
Search