MHS Boilers Ltd ©
191007
31
∆
t 20 K
Pump data
Nominal
flow
rate Q
Boiler
resistance
nom. flow
R
Pump type
WILO
(Equivalent or
better)
Pump
speed
Pump
head at
nom.
flow Q
Available
head at
nom.
flow Q
Maximum*
Power
consumption
Type
m
3
/h
KPa
KPa
KPa
W
WM/45 1.68
14
RS
25/6-3 max 40
26
93
WM/65 2.57
20
RS 25/7-3
PWM/3c
max.
49
29
132
WM/85
3.38
25
RS 25/7-3
PWM/3c
max.
40
15
132
WM/100
3.78
28
TOP-S 30/7
3
52
24
195
WM/120
4.70
30
TOP-S 30/7
3
42
12
195
Table 9 Water flow quantity and pump data for the WM
Maximum power consumed is given in pump position 3
WM/100 & 120 Wilo pumps type shown for guidance, equivalent or better pump can be utilised.
When using another ∆t you can use the following formula for calculating the flow rate and
resistance of the boiler.
After this you have to check the available head of the pump.
The boiler has a pump control circuit. When the boiler is enabled, the pump is switched on. If the
boiler is disabled, the pump will continue to run for a few minutes more. This run on time can be
adjusted. The standard time is 2 minutes.