WM Connecting terminals
The operation of the appliance can be influenced by externally generated signals applied to the
appropriate terminals.
Rear Of KM628 Boiler Controller
Terminal Designation
Terminal #s
Voltage
Screened
Cable
(Earthed Screening)
Description/Operation/Function
6 & 7
< 25V
-
Do Not Use
Internal Resistor for Hot Water Generation Control via Volt Free Enable
21 & 22
(Not Polarity Sensitive)
230V -
Hot Water Volt Free Enable.
(Via Time Switch/Room Thermostat/BMS)
13 <
25V -
Do Not Use
(Primary PWM + Pump Output)
12 <
25V -
Do Not Use
(Primary PWM - Pump Output)
11 <
25V
Yes
BM8 / KKM8 / E8 SCOM + Data Input
(KKM8 & E8 Communication via a COCO2 Unit)
10 <
25V
Yes
BM8 / KKM8 / E8 SCOM - Ground Input
(KKM8 & E8 Communication via a COCO2 Unit)
9 <
25V
Yes
0-5 Volt Control Signal Input.
(If not in use link to terminal 8)
8 <
25V
Yes
0-5 Volt Control Signal Input.
(If not in use link to terminal 9)
7 & 6
< 25V
Yes
Hot Water Sensor (SPFS).
5 & 4
230V
-
Heating Volt Free Enable.
(Via Time Switch/Room Thermostat/BMS)
3 & 1
230V
-
Safety Interlock Volt Free Enable
(For use with ventilation interlocks/gas pressure switch etc.)
2 230V -
Switched
Neutral
1 230V -
Switched
Live
N
230V
-
Permanent Neutral
L1 230V -
Permanent
Live
(Max 5 Amp)
E
230V
-
Common Permanent Earth
ST2 1&2
< 25V
Yes
Outside Air Sensor (AFS)
(Mounted on North Facing Wall)(BM8 Required to activate weather compensation)
ST11 2 & 1
230V
-
Hot Water Charging Pump 230V Output (2 Live, 1 Neutral)
(Max 1 Amp)
ST11 4 & 3
230V
-
Boiler Pump 230V Output (4 Live, 3 Neutral)
(Max 1 Amp)
ST32 1 & 2
< 25V
Red Jumper
Cascade Bus Power Interrupt
(Apply Jumper ton boilers 3 – 8 on KKM8 Controlled Systems)
Relay Legend
Relay Tag
Coil Voltage
Switching Voltage
Description/Operation/Function
K1
230V
< 25V
Internal Safety Interlock / Switching Flow switch and Air Pressure Switch Terminals
K2
230V
< 25V
External Safety Interlock / Switching Flue Gas sensor
K4
230V
230V
Gas Valve out for WM 120 units only (230V Gas Valve)
K5
230V
230V
Gas Valve out for WM 120 units only (230V Gas Valve)
K6
230V
< 25V
Hot Water Volt Free Enable activation / Switching substitute resistors