- Calibration of the room sensor
- Delay to flow temperature compensation due to external temperature up to a maximum of
3 hours
- Holiday Programme
- Frost protection system based on external temperature or room temperature
- Remote activation via telephone if no external room sensor fitted (external relay required)
- Optimisation of compensation slope based on room temperature and external temperature
with optimum start time adjustment
- Hot water Anti-legionella bacteria function
- Option of switching off internal room sensor
- 2-wired communication (scom-bus)
- Display in 6 different languages
- External display of KM628 functions with display of status, operating hours, number of starts,
degree of modulation and temperatures.
BM8 Room Unit
Room Unit Mounting Plate Wiring Terminals
Terminal Designation
When connected to a Single Ultramax Boiler (2 Wire SCOM)
Terminal #s
Voltage
Screened Cable (Earthed
Screening)
Description/Operation/Function
3 & 5
(Polarity Sensitive)
<25V
Yes
SCOM Communication to boiler
(3 - & 5 +)
3 & 6
(Not Polarity Sensitive)
<25V
Yes
Tamperproof RFB Remote
Sensor or Volt Free Enable
1 & 2 & 4
-
-
Not Used
When connected to a KKM8 or E8 Manager/Controller via a COCO2 (4 Wire CAN)
Terminal #s
Voltage
Screened Cable (Earthed
Screening)
Description/Operation/Function
1 & 2 & 3 & 4
(Polarity Sensitive)
<25V
Yes
CAN Communication to Controller
1 H, 2 L, 3 –, 4 +
3 & 6
(Not Polarity Sensitive)
<25V
Yes
Tamperproof RFB Remote Sensor
or Volt Free Enable
5
-
-
Not Used