Instructions GD0 9

3.1.3 

List of cables

Figure 13

3.2 

Preparing the Electrical System

E

3.2.1 

Connection to the Electrical Mains

Although the connection of GD0 to the electrical mains is beyond the
scope of this manual, we wish to remind you that:

• The power supply line must be laid and connected by a qualified
professional electrician.

• Have a suitably protected 16A “schuko” outlet installed, where
you can plug in GD0.

• Make sure that the power supply cable does not hang over mov-
ing parts or hazardous areas. 

• The electric line must be grounded and protected against short
circuits; a bipolar disconnection device must also be present with
contact separation of at least 3mm, which allows the power sup-
ply to be disconnected during the installation and maintenance of
the GD0.

With the exception of the plug and the power cable, the rest of the sys-
tem uses extra-low voltage (approx. 24V); the wiring can therefore be
done by personnel that is not properly qualified, provided that all the
instructions in this manual are carefully observed.

After selecting the position of the various devices (refer to figure 13) you
can start preparing the conduits for the electrical cables connecting the
devices to the control unit.

The shock-resistant conduits are designed to protect the electrical
cables and prevent accidental breakage.

Install any fixed control close to the door but away from moving parts and
at a height of 1.5m.

WARNING: the cables used must be suitable for the type of installation; for example, an H03VV-F type cable is recommended for indoor
applications.

Note 1:

For the PHOTO, STOP and OPEN cables, there are no special contraindications to the use of a single cable that groups together multiple

connections; for example, the STOP and OPEN inputs can be connected to the KS1 selector switch using a single 4x0.25mm

2

cable.

Table 5: List of cables

Connection

Cable type

Maximum length allowed

[A] STOP input 

2x0.25mm

2

cable

20m (note 1)

[B] OPEN input 

2x0.25mm

2

cable

20m (note 1)

[C] PHOTO input

TX 2x0.25mm

2

cable

RX 2x0.25mm

2

cable

20m (note 1)

[D] FLASH light output 

2x0.5mm

2

cable

20m

[E] Radio aerial 

RG58 type shielded cable

20m (recommended less than 5m)

The cables required for the installation of GD0 may vary depending on the type and quantity of devices to be installed; figure 13 shows the cables
needed for a typical installation; no cable is supplied with GD0.

D

B

A

C

C

Summary of Contents for GD0

Page 1: ...Installation instructions and warnings English IST GD0 GB 4865 Rev 00 del 15 03 2005 MhouseKit GD0 For the automation of a sectional or overhead door...

Page 2: ......

Page 3: ...ent that liquid substances have penetrated inside the automation devices immediately disconnect the power supply and contact the MHOUSE customer service department The use of GD0 in these conditions c...

Page 4: ...stops E GD0K gearmotor 2 2 Description of the automation A B Figure 1 2 Product description 2 1 Applications GD0 is a set of components designed for the automation of sectional or overhead doors in re...

Page 5: ...of devices GD0K is an electromechanical gearmotor consisting of a 24V direct cur rent motor It features a mechanical release mechanism with cord that allows you to move the door manually in the event...

Page 6: ...nits The transmission of the command is confirmed by the LED A an eyelet B allows them to be hung on a keyring Figure 7 B A The pair of PH0 wall mounted photocells once they are connected to the contr...

Page 7: ...e guide and the brackets to the ceiling The head of the guide will have to bear all the strain of opening and closing the door the ceiling mounted brackets will have to bear all the weight of GD0 In b...

Page 8: ...m 7 2m2 max width max imum torque 55kg Overhead garage doors 240cm max height 270cm 6 48m2 max width maximum torque 55kg The shape of the door and the climatic conditions e g presence of strong wind m...

Page 9: ...ces refer to figure 13 you can start preparing the conduits for the electrical cables connecting the devices to the control unit The shock resistant conduits are designed to protect the electrical cab...

Page 10: ...and related washer as in fig 18 7 Hook the upper carriage E to the lower carriage C and place the entire carriage assembly inside the guide as in fig 19 8 Assemble the Guide B head as in fig 20 This...

Page 11: ...d lift the guide from the front and secure it with two screws anchors or riv ets depending on the type of surface 3 Secure the mounting brackets L using the screws M and nuts N and choosing the hole t...

Page 12: ...all the strain resulting from opening and clos ing the door 9 Loosen the screws in the two mechanical stops then place the front mechanical stop O before the carriage Figure 33 Push the carriage hard...

Page 13: ...he edge of the door With sectional doors the photocells can be mounted outside whereas with overhead doors they can only be mounted inside outside they would obstruct the movement of the door Point tr...

Page 14: ...the hole for the passage of the cables in the bottom or side depending on the installation position using a screwdriver 5 Mark the drilling points using the bottom as reference and make sure that the...

Page 15: ...ove the small piece of wire between ter minals 3 and 7 and make the connections as in Fig 56 if using the flashing light aerial remove the piece of wire which is con nected to terminal 2 and connect t...

Page 16: ...ly an external aerial can be used or the small piece of wire that is already connected to the terminal can be left which acts as an aerial 3 4 OPEN input for manoeuvre control devices Normally Open ty...

Page 17: ...t manoeuvres are not interrupted by any commands If the manoeuvres are not completed repeat the recognition procedure starting from step 1 The position recognition stage can be repeated at any time in...

Page 18: ...en carefully observed 2 Using the selector switch if provided or the radio transmitter test the opening and closing of the door and make sure that the door moves in the intended direction The test sho...

Page 19: ...directions provided in the corre sponding maintenance schedule 4 Maintenance 3 7 2 Commissioning The commissioning operations can be performed only after all the tests have been successfully carried...

Page 20: ...force OPEN function 1 Open Stop Close Stop Press button T2 once 2 Open Stop Close Open Press button T2 twice 3 Open Open Open Open opening only Press button T2 three times The following chapters descr...

Page 21: ...as described in the Photocell instructions in the event there are two pairs of photocells that could interfere with one another 5 3 2 STOP Input STOP is the input that causes the immediate interruptio...

Page 22: ...n partially Open only and Close only can be associated to each button In Mode 2 each button requires a separate memorization stage 1 Press button P1 figure 71 on the control unit as many times as the...

Page 23: ...ion stage or in case of failure Table 10 Symptoms probable cause and possible solution The radio transmitter does not emit any sig nal the LED A does not light up Check to see if the batteries are exh...

Page 24: ...s pause 2 flashes Triggering of a photocell At the starting of the manoeuvre one or more photocells do not enable it check to see if there are any obstacles If there is an obstacle impeding the movem...

Page 25: ...tion in progress On Memorization in Mode 1 This is normal during memorization in mode 1 which lasts maximum 10s Series of quick flashes from 1 to 4 Memorization in Mode 2 This is normal during memoriz...

Page 26: ...r 200W Insulation class 1 a safety grounding system is required Emergency power supply Flashing light output For visual signalling devices with 12V lamp maximum 21W Courtesy light 12V lamp maximum 21...

Page 27: ...ontrol units Lamp 12V 21W BA15 socket automotive type lamp Power supply contacts The device can only be connected to the FLASH output terminals 9 10 and ARIEL input 1 2 of the MHOUSE automation contro...

Page 28: ...Operating ambient temperature 20 50 C Use in acid saline or potentially explosive atmosphere No Protection class IP40 suitable for use indoors or in protected environments Dimensions weight 72 x 31 h...

Page 29: ...L of 9th March 1999 concerning radio equipment and telecommunications terminal equipment and mutual recognition of their conformity According to the following standards ETSI EN 300 220 3 ETSI EN 301 4...

Page 30: ......

Page 31: ...nufacture Location address Satisfies the essential requirements of the following Directives 98 37 EC Machine Directive 89 336 ECC Electromagnetic Compatibility Directive 73 23 ECC Low Voltage Directiv...

Page 32: ......

Page 33: ...control or key operated selector switch If the safety devices enable the operation the door will open normally otherwise actuate the control again within 3 seconds and keep it actuated 2 After approx...

Page 34: ...balanced door could cause injury If the range of the remote control is significantly diminished and the light emitted by the LED is feeble the remote control battery is probably exhausted The remote c...

Page 35: ......

Page 36: ...Mhouse Via Pezza Alta 13 Z I Rustign 31046 Oderzo TV Italia Tel 39 0422 20 21 09 Fax 39 0422 85 25 82 info mhouse biz www mhouse biz...

Reviews: