ProCon HT 150 / HT 225
7. Technical documentation
7.10 Technical data ProCon HT 150 / HT 225
Typ
e
ProCon HT 150 H
ProCon HT 225 H
Product ID number
CE -
CE -
Category
II2ELL3/P
II2ELL3/P
Volume of hot water in boiler
l
30
35
Boiler weight
kg
250
270
Measurements (L x B x H)
mm
1650 x 680 x 1030
Hot water connections
FlangeDIN 2631 DN 40 / 48.3 PN 6
Gas connection
R 1¼
Flue gas connection
DN 160
Inlet air connection
DB 125
Inlet air/flue gas-connecting pieces
DN 160
Condensed water run-up
Hose spout D = 20 mm
Condensed water drain
DN 20, ¾“ AG, flat sealing
Rated thermal load
kW
15.0 – 149.2
15.0 – 216.0
Rated thermal load 80/60°C
kW
14.5 – 143.2
14.5 – 206.0
Rated thermal load 50/30°C
kW
16.0 – 155.0
16.0 – 225.0
Degree of efficiency 40/30°C
%
109.5
Gas types
Natural gas E /
LL
Liquid gas
Natural gas E
/LL
Liquid gas
Nozzle-
∅
mm
15.0
10.0
15.0
10.0
CO
2
content
Vol.%
9.0
11.0
9.0
11.0
Flue gas temperature 80/60
°C
74
Flue gas mass flow rate
kg/s
0.0697
0.0643
0.1010
0.0931
Manometer pressure on the flue gas connecting
pieces
Pa
200
200
200
200
Permissible flue gas lead
B
23
, C
33
, C
43
, C
53
, C
63
, C
83
pH value of condensed water
4...5.5
Gas connection pressure
Natural gas E /
LL
Liquid gas
Natural gas E
L
Liquid gas
Min.
mbar
18.0
30.0
18.0
30,0
Max.
mbar
30.0
50.0
30.0
50.0
Maximum gas connection pressure, P
imax
mbar
70
Electrical connection
V/Hz
230 / 50
Max. electr. power consumption
W
690
800
Max. operating pressure
bar
3.0
Min. system pressure
bar
0.5
Switching on threshold hydraulic pressure switch
bar
0.8
Flow rate at
∆ϑ
= 20°C
l/h
6500
9600
Max. flow temperature
°C
90°
63