ProCon HT 150 / HT 225
4. Hydraulic schemes
•
Component
s
Compo
nent
Typ
e
Code number
Annotation
ProCon HT master
Cascade
96.30000-7082
Included in the scope of delivery:
Outdoor sensor QAC 31 as well as Cascade
controller RVA 47, 2 strap-on sensors QAD 21, bus
module OCI 420
ProCon HT slave
Cascade
96.30000-7084
Water deflector
(see Total price list)
2 Control units
RVA 63.280/380
94.80100-5510
2 Wall-mount enclosure for
RVA 63
94.85301-5004
3 x Flow sensor
QAD 26
94.19314-5005
94.19314-5002
Length 4 m
Domestic water sensor
QAZ 21
94.19314-5003
Length 6 m
•
Electrical connections
Component
Connection to
Annotation
Outdoor sensor
OS terminal
Two wire bus
Bus terminal
Bus connection between the boiler master
and slave
HC flow sensor
Boiler return sensor
Lustre terminal in the appliance
The strap-on sensors included in the scope
of delivery must be place on the structure
of the water deflector.
HC pump 1
RVA 63.280
Q2, N,
Flow sensor MK 1
RVA 63.280
B12, M
Pump MK 1
RVA 63.280
Q6,
Mixer motor MK 1
RVA 63.280
Y5, Y6, N,
Pump MK 2
RVA 63.280
Q2, N,
Mixer motor MK 2
RVA 63.280
Y1, Y2, N,
Flow sensor MK 3
RVA 63.280
B12, M
Pump MK 3
RVA 63.280
Q6,
Mixer motor MK 3
RVA 63.280
Y5, Y6, N,
Domestic water sensor
RVA 63.280
B3, M
Domestic water charge pump
RVA 63.280
Q3, N,