7. Technical documentation
7.8
Technical data RVA 47
Voltage supply
Rated voltage
AC 230 V (±10 %)
Rated frequencies
50 Hz (±6 %)
Power consumption
Max. 7 VA
Requirements
Protection class (for proper installation)
II, according to EN60730
Protection type (for proper installation)
IP 40, according to EN60529
Electromagnetic stability
Conforms to EN50082-2 standards
Electromagnetic emissions
Conforms to EN50081-1 standards
Climatic conditions
In operation in accordance with
IEC 721-3-3
Temperature
In storage in accordance with IEC
721-3-1
Temperature
During transportation in
accordance with IEC 721-3-2
Temperature
Class 3K5 (without condensation)
0...50°C
Class 1K3
-25...70°C
Class 2K3
-25...70°C
Dirt
In accordance with EN60730
General Environment
Mechan. conditions
In operation in accordance with IEC 721-3-3
Class 3M2
In storage in accordance with IEC 721-3-1
Class 1M2
IEC 721-3-2
Class 2M2
Mode of operation
In accordance with EN60730 Abs. 11.4
1b
Output relay
Voltage range
AC 24...230 V
Rated flow
AC 0.02...2 (2) A
Switch-on peak
max. 10 A in the course of max. 1 sec
Fused connection
max. 10 A
Approved lead length for PPS:
(Phone cable
φ
0.8mm, 2-wire interchangeable)
Max. Lead length Central device/Peripheral device
75 m.
Max. Total lead length (Sum total of all cords)
250 m
Bus expansion
Approved lead length for LPB:
(Cu-cable1.5 mm
2
, 2-wire not interchangeable)
With control bus feed (for each controller)
250 m
With central bus feed (bus feed/controller)
460 m
Bus load factor
E = 3
Approved Sensor lead
lengths
Ø 0.6 mm
max. 20 m
2
1.0 mm
2
1.5 mm
max. 80 m
max. 120 m
61