42
3511
Power range, lower limit (Pmin)
20
%
3512
Power range, upper limit (Pmax)
85
%
3530
Release limit producer sequence
25
°C*min
3531
Reset limit producer sequence
20
°C*min
3532
Restart lock time
30
s
3533
Switch-on delay lag heat source
1
min
3534
Forced time basic stage during
producer turn on
0
s
3540
Time to automatic producer sequence
switching
10
h
3541
Exclude at automatic producer
sequence switching
none
3544
Leading producer
Producer 1
3550
Protective start up cascade pump
Off
3560
Cascade return setpoint minimum
8
°C
3561
Cascade return setpoint minimum
OEM
8
°C
3562
Cascade return flow
On
3570
Actuator running time return temp
limitation
120
s
3571
P-band (Xp) return temp limitation
32
°C
3572
Integral action time (Tn) return temp
limitation
120
s
3590
Min temp differential hydraulic
balancing
2
°C
Solar
3810
Temp differential on solar
8
°C
3811
Temp differential off solar
4
°C
3812
Min charging temperature DHW
storage tank
-------
°C
3813
Temperature differential ON buffer
-------
°C
3814
Temperature differential OFF buffer
-------
°C
3815
Min charging temperature buffer
-------
°C
3816
Temperature differential swimming
pool ON
-------
°C
3817
Temperature differential swimming
pool OFF
-------
°C
3818
Min charging temperature swimming
pool
-------
°C
3822
Charging priority storage
DHW storage
tank
3825
Charging time relative priority
-------
min
3826
Wait time relative priority
5
min
3827
Wait time parallel operation
-------
min
3828
Start delay secondary pump
60
s
3830
Collector Start function
-------
min
3831
Min collector pump running time
20
s