44
4795
Comparative temperature return
diverting
Buffer sensor
B42
4796
Operating action return diverting
Return temp
rising
4800
Buffer partial charging setpoint
-------
°C
4810
Full charging buffer
Off
4811
Full charging temperature min
8
°C
4813
Full charging sensor
With B42/B41
DHW storage tank
5010
DHW charging
Several
times/day
5020
DHW flow setpoint boost
16
°C
5021
DHW transfer boost
8
°C
5022
DHW recharging control
With sensors B3
and B31
5024
DHW switching differential
5
°C
5030
DHW charging time limitation
150
min
5040
DHW discharging protection
Automatically
5050
DHW charging temperature max
80
°C
5051
DHW storage tank temperature max
90
°C
5055
DHW storage tank return cooling
temperature
80
°C
5056
DHW storage tank return cooling
Producer/HC
Off
5057
DHW storage tank return cooling
Collector
Off
5060
DHW electric immersion heater
operating mode
Backup mode
5061
DHW electric immersion heater release
DHW release
5062
DHW electric immersion heater
control
DHW sensor
5070
DHW automatic push
On
5071
charging priority time push
0
min
5085
DHW storage tank over temperature
drop
On
5090
DHW storage tank with buffer
No
5092
DHW storage tank with
precontr/primary pump
No
5093
DHW storage tank with solar
Yes
5120
Mixing valve setpoint boost DHW
precontr
2
°C
5124
Actuator running time DHW precontr
120
s
5125
P-band (Xp) DHW precontr
32
°C
5126
Integral action time (Tn) DHW
precontr
120
s
5130
Transfer strategy
Always
5131
Comparative temperature transfer
DHW sensor B3