Removing the ignition and ionisation electrodes
Check the electrode, especially the distance between the two
pins (4 ± 0,5 mm). Replace electrode if necessary.
1: Carefully pull off the connecting cable (
1
)
from the ignition electrode (
7
).
2: Loosen the two fixing nuts (
2
) on the ignition
electrode and remove the entire electrode.
3: Replace the gasket (
3
) and fit the new ignition
electrode.
4: Carefully pull off the connecting cable from the
ionisation/monitoring electrode (
3
).
5: Loosen the two fixing nuts (
4
) on the ionisation
electrode and remove the entire electrode.
6: Replace the gasket (
5
) and fit the new ionisation/
monitoring electrode.