Function value 2 H2 module 2
-1000 - 5000
0
6062
Function input H2 module 3
None, Optg mode change HCs +
DHW, Optgmode changeover DHW,
Optgmode changeover HCs, Opt
mode changeover HC1, Opt
changeover HC2, Opt changeover
HC3, Heat generation lock,
Error/alarm message, Consumer
request VK1, consumer request VK2,
release swi pool source heat, Excess
heat discharge, release swi pool
solar, Operating level DHW,
Operating level HC1, Operating level
HC2, Operating level HC3, Room
thermostat HC1, Room thermostat
HC2, Room thermostat HC3, DHW
flow switch, DHW thermostat, Pulse
count, Checkb sign flue gas damper,
Start prevention, Boiler flow switch,
Boiler pressure switch, Consumer
request VK1 10V, Consumer request
VK2 10V, Pressure measurement
10V, Output request 10V
None
6063
Contact type H2 module 3
Normal closed, Normal open
Normal open
6065
Voltage value 1 H2 module 3
0 - 10
0
Volts
6066
Function value 1 H2 module 3
-1000 - 5000
0
6067
Voltage value 2 H2 module 3
0 - 10
0
Volts
6068
Function value 2 H2 module 3
-1000 - 5000
0
6072
Signal output UX
0...10V, PWM
PWM
6078
Function output UX2
None, Boiler pump Q1, DHW pump
Q3, DHW intermcir pump Q33, Heat
circuit pump HC1 Q2, Heat circuit
pump HC2 Q6, Heat circuit pump
HC3 Q20, Collector pump Q5, Solar
pump extexch K9, Solar pump buffer
K8, Solar pump swi pool K18, Instant
heater pump Q34, Solid fuel boiler
pump Q10, Bypass pump Q12
None
6085
Function output P1
See Para 6078
Boiler pump Q1
6089
Function output UX3
See Para 6078
None
6097
Sensor type collector
NTC, Pt 1000
NTC
6098
Readjust collector sensor
-20 - 20
0
°C
6100
Readjust outside sensor
-3.0 - 3.0
0
°C
6101
Sensor type flue gas temp
NTC, Pt 1000, NTC 20k
NTC
6102
Readjust flue gas sensor
-20 - 20
0
°C
6110
Time constant building
0 - 50
15
H
6116
Time constant setp. compens.
0 - 14
0
Min.
6117
Central setp. compensation
----/1 - 100
5
°C
6118
Setpoint drop delay
----/1 - 200
----
°C
6120
Frost protection plant
Off, /on
Off
-
6127
Pump/valve kick duration
0 - 51
30
S
6140
Water pressure max
----/0.0 - 10.0
3
Bar