34008486EN/AA
- Page 44
8. Appendices
8.1 Technical specifications
(1) If the output voltage is 200V - 250V, the output power is 15 kVA / 12 kW.
(2) With one
EXB
module or more, the standard output power is 20 kVA / 16 kW.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V /
230V
/ 240V / 250V using the
UPS Config
software.
(5) Frequency-converter mode is programmable using the
UPS Config
software.
Pulsar MX Frame 15000 RT
Pulsar MX Frame 20000 RT
Pulsar MX EXB
Output power
15 kVA
(1)
/
13.5 kW
(2)
20 kVA
(1)
/
18 kW
(2)
Electrical supply network
◗
Rated input voltage
◗
Input voltage range
◗
Frequency
◗
Power factor
Harmonic distortion
◗
Leakage current
Single phase 230 V / Three phase 400 V
120 / 156 V to 280 V
(3)
50/60 Hz (autoselection)
> 0,99
> 5%
1:1 20 mA max. / 3:1 30 mA max.
Load output
◗
Voltage
◗
Frequency
◗
Harmonic distortion
◗
Overload capacity
Single phase 230 V ±3%
(4)
50/60 Hz ±0,5%
(5)
1:1 < 10% / 3:1 < 20%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
Battery
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
Two 15 x 12 V - 5 Ah
strings, sealed lead
acid, maintenance free
Environment
◗
Operating temperature range
◗
Relative humidity
◗
Storage temperature range
◗
Altitude
◗
Noise level
0°C to 40°C
20% to 90% (non-condensing)
-25°C to 40°C
0 to 1000 m without derating
< 51 dBA
Summary of Contents for Pulsar MX Frame 15000 RT