                                                Important Safety Instructions 

True Online 6-20k UPS User Manual

 

IMPORTANT SAFETY INSTRUCTIONS 

SAVE THESE INSTRUCTIONS 

This manual contains important safety instructions. Read all safety and operating 

instructions before operating the uninterruptible power systems (UPS). Adhere to all 

warnings on the unit and in this manual. Follow all operating and user instructions. This 

equipment can be operated by individuals without previous training. 

This product is designed for commercial/industrial use only. It is intended for use with lift 

support and other designated “critical” devices. Maximum load must not exceed that shown 

on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, 

consult your dealer or local representative. 

This UPS is designed for use on a properly grounded (earthed), 220/230/240VAC, 50 or 

60Hz supply. The factory default setting is 220VAC/50Hz. Installation instructions and 

warning notices are in this manual. 

The UPS 06-20@220/230/240VAC is designed for use with a three-wire input (L,N,G). 

 WARNING 

THE BATTERY CAN PRESENT A RISK OF ELECTRICAL SHOCK AND 

HIGH SHORT CIRCUIT CURRENT. FOLLOWING PRECAUTIONS 

SHOULD BE OBSERVED BEFORE REPLACING THE BATTERY. 

z

 

Wear rubber gloves and boots. 

z

 

Remove rings, watches and other metal objects. 

z

 

Use tools with insulated handles. 

z

 

Do not lay tools or other metal objects on the batteries. 

z

 

If the battery is damaged in any way or shows signs of leakage, contact your local 

representative immediately. 

z

 

Do not dispose of batteries in a fire. The batteries may explode. 

z

 

Handle, transport and recycle batteries in accordance with local representative. 

WARNING 

ALTHOUGH THE UPS HAS BEEN DESIGNED AND MANUFACTURED 

TO ENSURE PERSONAL SAFETY, IMPROPER USE CAN RESULT IN 

Summary of Contents for HT1106L

Page 1: ...ned for use on a properly grounded earthed 220 230 240VAC 50 or 60Hz supply The factory default setting is 220VAC 50Hz Installation instructions and warning notices are in this manual The UPS 06 20 22...

Page 2: ...OBSERVE THE FOLLOWING PRECAUTIONS z Turn off and unplug the UPS before cleaning it z Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners z Never block or insert any objects into the...

Page 3: ...3 INVERTER 7 3 4 BATTERY CHARGER 8 3 5 DC TO DC CONVERTER 8 3 6 BATTERY 8 3 7 DYNAMIC BYPASS 8 4 PRODUCT SPECIFICATION AND PERFORMANCE 9 4 1 MODEL DESCRIPTION 9 4 2 PRODUCT SPECIFICATION AND PERFORMA...

Page 4: ...ERY MAINTENANCE 27 9 NOTES FOR BATTERY DISPASAL AND REPLACEMENT PROCEDURES 28 9 1 BATTERY DISPOSAL 28 9 2 BATTERY REPLACEMENT PROCEDURES 28 10 TROUBIE SHOOTING 29 10 1 CHECKING UPS STATUS 29 10 2 ADJU...

Page 5: ...e substance This UPS contains no user serviceable parts except the internal battery pack The UPS on off push buttons do not electrically isolate internal parts Under no circumstance attempt to gain ac...

Page 6: ...spikes and complete power failure that may interrupt computer operations cause data loss and even damage equipment The UPS protects equipment from these disturbances The UPS is a compact on line UPS A...

Page 7: ...2 3 4 5 6 7 8 9 10 11 12 3 4 5 6 7 8 9 10 11 12 3 4 5 6 8 7 11 10 9 12 13 13 13 6K long backup model 10K long backup model 6K standard model 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 10 10 11 11 12 13 13 10K...

Page 8: ...ons 1 SNMP card slot 2 Dry contactor slot 3 USB port 4 RS232 5 EPO 6 Parallel ports 7 Fans 8 Reserved customer function 9 External battery connector Optional for standard model 10 Internal maintenance...

Page 9: ...nsuring that the waveform of the input current used by the UPS is near ideal Extracting this sine wave input current achieves two objects z The utility power is used as efficiency as possible by the U...

Page 10: ...nclude value regulated non spoilable lead acid batteries inside To maintain battery design life operate the UPS in an ambient temperature of 15 25 C 3 7 Dynamic Bypass The UPS provides an alternate pa...

Page 11: ...0KVA 18KW Frequency Hz 50 60 Input Voltage 176 275 VAC Current 34A max 57A max 87A max 115A max Battery Voltage 192VDC 192VDC 192VDC 192VDC Current 37A max 60A max 90A max 120A max Output Voltage 220V...

Page 12: ...ted in use please refer to the following Altitude M 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating Power 100 95 91 86 82 78 74 70 67 Output Voltage Regulation Power Factor Frequency tolerance D...

Page 13: ...from water inflammable gas and corrosive agents 2 Ensure the air vents on the front and rear of the UPS are not blocked Allow at least 0 5m of space on each side 3 Condensation to water drops may occ...

Page 14: ...TICE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed For the...

Page 15: ...and the input and output terminals are connected tightly NOTICE Please make sure that if there is a copper bar shorting input A B C terminal for UPS 15KL 20KL or else you must contact with supplier 7...

Page 16: ...8 hours before use After connection turn the input breaker in the ON position the UPS will charge the batteries automatically You can also use the UPS immediately without charging the batteries first...

Page 17: ...You must connect the external battery cable to the battery first if you connect the cable to the UPS first you may encounter the hazardous of electric shock The positive pole of the battery is connec...

Page 18: ...ing diagram in the next page and opt suitable breaker The requirement of the output wiring is as follows When the distance between the UPSs in parallel and the breaker panel is less than 20 meters the...

Page 19: ...Installation True Online 6 20k UPS User Manual 17 a Wiring Diagram of 6K L S 10K L S...

Page 20: ...nput breaker UPS1 input breaker utility UPS2 battery breaker UPS1 battery breaker UPS2 output breaker UPS1 output breaker PE Input A N L Battery input Output N B C PE Input A N L Battery input Output...

Page 21: ...INV mode When the last one completes the shutdown action each unit will shut down the inverter simultaneously and transfer to Bypass mode It is easy to operate the equipment with no previous training...

Page 22: ...s set in automatically start mode 2 Press on off directly when there is no main input press again to start UPS 3 Press on off to shutdown inverter when UPS is in normal mode 4 Press on off to shutdown...

Page 23: ...s indicator green bypass is normal dark UPS is in normal mode and bypass is normal red bypass fault red flicker bypass alarm BAT Battery indicator green battery charge green flicker battery discharge...

Page 24: ...tion Set language contrast communication set SNT Modbus Modbus set Function function 1 transfer to bypass escape fault clear mute on off function 2 battery test maintenance test stop test History log...

Page 25: ...of the battery pack is in the ON position this step only for long backup time model 2 Press the ON OFF button once to power on the LCD then press ON OFF button again choose ON to enter 3 A few second...

Page 26: ...normal and all the UPSs transfer to the INV mode normally Notice close output 1 breaker and 2 breaker as fig 7 to make sure that output of every UPS are shorted before starting UPS or else the paralle...

Page 27: ...o the Maintenance Mode the circuit breakers CB are in the following status Input and Output are closed in the on position the Maintenance Bypass is open as it is shown in the figure above 2 Transfer t...

Page 28: ...ry terminal of positive and negative for the long run type UPS open the battery CB 3 Transfer back to Normal Mode After the maintenance is finished follow the procedures below to transfer the UPS to N...

Page 29: ...PS should be charged once every 4 to 6 months if it has not been used for a long time zIn the regions of hot climates the battery should be charged and discharged every 2 months The standard charging...

Page 30: ...ed from the input potential circuit There may be hazardous voltage between the battery terminals and the ground 8 Even though the input breaker is disconnected the components inside the UPS are still...

Page 31: ...op and contact your local representative or Channel Support z Check whether the battery is discharging When the utility input is normal the battery should not discharge If the UPS is operating in Batt...

Page 32: ...broken IGBT drivers are lost 17 A1 1 Reserved 18 2 Reserved 19 3 Reserved 20 4 Reserved 21 5 Reserved 22 6 Reserved 23 7 Reserved 24 8 Reserved 25 9 Input voltage Fault OK Fault Input voltage out of r...

Page 33: ...38 6 Negative bus under voltage OK Fault UPS requires service 39 7 Battery reversed OK Fault Check if the battery wires connection is OK 40 8 Reserved 41 9 Reserved 42 10 Reserved 43 11 Reserved 44 1...

Page 34: ...hutdown normal shutdo wn 66 2 INV protect OK Fault 67 3 Transfer times limit in one hour OK Fault Transfer times between inverter and bypass is over 5 times in one hour 68 4 Reserved 69 5 Reserved 70...

Page 35: ...6 Reserved 81 A5 1 Reserved 82 2 Output shorted OK Fault Shutdown UPS and open output breaker check if load is effective or short internally check if output connector is shorted 83 3 Battery test None...

Page 36: ...ameter can be set now 4 Input voltage setting is activated Press to select the rated input voltage The voltages are available for customer such as 110V 120V 127V 200V 208V 220V 230V 240V 5 Press ENTER...

Page 37: ...ng Press to select the rated frequency 50Hz and 60Hz are available for selection 7 Press ENTER button to confirm frequency selection and the current parameters are shown on LCD as below 8 Shutdown UPS...

Page 38: ...lt 2 Normal warning Low Voltage UPS unusual 3 GND 4 Far away cut off Utility usual UPS cut off Rectifier and Inverter Battery Mode cut off the whole system High Voltage Far away cut off the machine 5...

Page 39: ...under emergency the function is triggered by customer s connector By shorting common open point NO with 24V EPO function is effective Far away EPO connector denotation Pins Name Denotation P1 24V 24V...

Reviews: