3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C-40
°
C <95% <1000m
0
°
C-70
°
C
NOTICE
:
If the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating
Power
100% 95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Crest ratio
±
1% 0.9
lag
±
0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 10
minutes
130% load: transfers to
Bypass mode after 1
minute
150% load :transfers to
Bypass mode after 0.5
minute and shutdown the
output after 1 minute
3:1
maximum