34008486EN/AA
- Page 21
2. Installation
Three phases input
Pulsar MX Frame must be fed from a 3-phase source with neutral.
UPS with common Normal and Bypass AC inputs
Main low-
voltage
switchboard
(MLVS)
load
Change in SEA between upstream and downstream or galvanic isolation required
Main low-
voltage
switchboard
(MLVS)
load
UPS with separate Normal and Bypass AC inputs
Main low-
voltage
switchboard
(MLVS)
load
Change in SEA between upstream and downstream or galvanic isolation required
Main low-
voltage
switchboard
(MLVS)
load
* The transformer is not necessary if:
Normal and Bypass AC inputs are connected to the same source,
and wires cross sections and wires lengths on Normal and Bypass inputs are identical,
and upstream protection is provided by only one switch with RCD (residual current device) for Normal and Bypass inputs.
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
*
Bypass AC
Normal AC
*