34008486EN/AA
- Page 16
2. Installation
2.4 Communication ports
Pulsar MX
RT
provides 3 communication methods that can be used simultaneously:
◗
2 COM ports provide RS232 or USB communications using MGE UPS SYSTEMS SHUT protocol. Compatible with most
power management software applications available into the enclosed
Solution Pac
CD-Rom. Please, note that both ports
cannot be used at the same time.
◗
The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.
◗
The two slots are compatible with any MGE UPS SYSTEMS communication card (check
www.mgeups.com
web site for
the complete list of compatible cards).
Connection to the RS 232 communication port
Connection to the communication port by relays
1 - Connect the RS232
(1)
communications
cable to the serial port on the computer
equipment.
2 - Connect the other end of the
communication cable
(1)
to the RS232
(2)
communications port on the UPS.
The
UPS
can now communicate with various
MGE UPS SYSTEMS power management
application software. Please note that the
configuration software is included with
Personal Solution Pac
for Windows.
(1)
Communication port by relay
◗
Pin 1: major alarm
◗
Pin 2: battery fault
◗
Pin 3: remote shutdown from external power (5 to 27 V DC/10 mA max).
◗
Pin 4: normal operation, not on battery, contact ( 48 V DC/2 A max)
◗
Pin 5: common
◗
Pin 6: operation on bypass,
◗
Pin 7: low battery warning
◗
Pin 8: load powered
◗
Pin 9: operation on battery
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.
Output relays specifications
◗
Voltage: 48 V DC max,
◗
Current: 2 A max,
◗
Power: 62.5 VA, 30 W.
Example: for 48 V DC, Imax=625 mA
1
2
1
5 4 3 2
9 8 7 6
1
n.o.
n.o.
n.o.
n.o.
n.o.
common
n.o.
n.o.
n.o. : contact normally open