2. Installation
Installation of communication card
Remote Power Off communication port
It is not necessary to shutdown the UPS
before installing a communications card.
1 - Remove the slot cover
(1)
secured by two
screws.
2 - Insert the communication card
(2)
in the
slot.
3 - Secure the card with both screws.
(1)
Remote Power Off communication port (RPO).
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize devices and
Pulsar MX Frame
with the RPO port, it is necessary:
◗
to use a two-position switch (Normally Open or Closed contact should be held more than 1 second to be taken into account).
◗
to connect to this RPO switch a device that allows to trip all breaker(s) located upstream
(1)
and downstream
(2)
Pulsar MX
RT. This can be achieved by means of a shunt trip.
(1) : If not, the output devices could be powered again through static switch when the two-position switch is released.
(2) : If not, the output devices will remain powered several seconds after the RPO activation.
Please, notice that the internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Remote power off contact normally open
Remote power off contact normally closed
◗
Signal:
- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.
Car
d Settings
RS232 Do
wnload
66074
UPS data
Reset
100 10
1 2 ON
ETHERNET
RS232
IP= MA
C=00E0D8FF855E
1
Car
d Settings
RS232 Do
wnload
66074
UPS data
Reset
100 10
1 2 ON
ETHERNET
RS232
IP= MA
C=00E0D8FF855E
2
1
RJ12 (6p6c)
5 4 3 2 1
6
5 V DC to 27 V DC
5 4 3 2 1
6
RJ12 (6p6c)
5 V DC to 27 V DC
Summary of Contents for Pulsar MX Frame 15000 RT
Page 2: ...34008486EN AA Page 2...