Installation and User Manual
Appendix C
Link to an IBM AS/400® Computer
The Galaxy PW™ can dialogue with an IBM AS/400® computer via a link in compliance with IBM communications
recommendations, thus enhancing the protection provided by your Galaxy PW™.
The IBM AS/400® computer must be configured for the link. This section describes the physical connections
required as well as the system values that must be modified on the AS/400®. For further information, consult the
following IBM documents:
◗
"Planning Guide, Appendix E" concerning physical connections.
◗
"Back-up and Recovery Guide", chapter 7 "Power Loss Recovery" concerning configuration of the AS 400®.
Connect and Configure the AS400 Link
Connections are made to the female client connector XR5 on the "Media Contacts 11" board. The corresponding
male connector is supplied; see Figure 3-12 below for the wiring diagram. A five-wire cable (not supplied) is required.
1.
On the AS/400® side, use a 9 or 15-pin SUB-D connector. (Depending on the type of AS/400®.)
2.
Certain values on the AS/400® must be configured to enable operation of the Galaxy PW™ — AS/400® link.
The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss
Recovery" of the "Back-up and Recovery Guide" for the AS/400®.
Configuration values:
◗
QUPSMSGQ: UPS message queue;
◗
QUPSDLYTIM: Uninterruptible power supply delay time;
◗
QPWRRSTIPL: Power restore IPL.
Appendices
A — 13
86-133060-00 A00
Summary of Contents for GALAXY PW 100
Page 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Page 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Page 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Page 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Page 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Page 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Page 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Page 102: ......
Page 103: ......