Legend:
nb of backups:
This is the number of times the load was supplied by the UPS from battery power
since the last reset.
nb of backups < 1 min:
This is the number of times the load was supplied by the UPS from battery power for
less than one minute, since the last reset.
1 min < nb of
This is the number of times the load was supplied by the UPS from battery power
backups < 3 min:
for more than one minute and less than three minutes, since the last reset.
nb of backups > 3 min:
This is the number of times the load was supplied by the UPS from battery power for
more than three minutes, since the last reset.
nb of overloads < 5’s:
This is the number of times the UPS was overloaded (output current greater than In)
for less than five seconds, since the last reset.
nb of overloads > 5’s:
This is the number of times the UPS was overloaded (output current greater than In)
for more than five seconds, since the last reset.
nb of times
This is the number of times the battery temperature was measured at over 25°C,
TBatt. > 25°C:
since the last reset.
FIGURES SINCE RESET
nb of backups:
0
nb of backups < 1 min:
0
1 min < nb of backups < 3 min:
0
nb of backups > 3 min:
0
nb of overloads < 5 s:
0
nb of overloads > 5 s:
0
nb of times TBatt. > 25°C:
0
Galaxy PW
™
UPS 100 to 225kVA
Operation
4 — 20
86-133060-00 A00
Summary of Contents for GALAXY PW 100
Page 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Page 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Page 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Page 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Page 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Page 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Page 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Page 102: ......