4.3
Operation with the Normal AC Source Restored
When normal AC source power
(1)
is restored or its voltage returns to within specified tolerances, the system
automatically returns to its normal operating mode described above (on the condition it did not reach the end of
battery power). If the end of battery power was reached (with the resulting inverter shutdown), the rectifier/charger
(A)
restarts automatically, but the inverter
(B)
must be restarted manually.
The rectifier/charger recharges the battery
(D)
which was discharged during the mains outage. During battery
charging, light
2
flashes green.
The message "BATTERY CHARGING" is displayed, together with the value of the recharging current and battery voltage.
Figure 4-7: Normal Operation Mode Indicator Diagram.
The battery charge cycle takes place in two steps: See Figure 4-8.
step 1:
the battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached.
step 2:
the battery is recharged at constant voltage equal to the charge level. The charging current gradually
decreases until reaching a specified low value (floating current).
For vented lead-acid batteries, the rectifier/charger supplies the charging voltage for 0 to 255 hours (parameter
defined by the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the
charging and floating voltages are the same.
NOTE
If the normal AC source failure is shorter than 0 to 255 seconds (default value = 30
seconds) (parameter defined by after-sales support department), the charger
automatically supplies the floating voltage given the low battery discharge.
1
2
AB
C
D
2
1
4
5
2
1
Operation
4 — 5
86-133060-00 A00
Summary of Contents for GALAXY PW 100
Page 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Page 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Page 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Page 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Page 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Page 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Page 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Page 102: ......
Page 103: ......