Installation and User Manual
4.2
Operation in On-line Mode
4.2.1
Normal Operation
Normal AC source power is available, see Figure 4-5.
◗
Lights
1
,
4
and
5
shine green on the control panel.
-The power necessary for the load is provided by the normal AC source
(1)
through the rectifier/charger
(A)
and the inverter
(B)
. The rectifier/charger
(A)
also supplies the power to float charge and recharge the
battery if any.
The output voltage (DC) is regulated to supply:
◗
The float-charging or the recharging voltage for vented lead-acid or Ni/Cd batteries.
- a single charge voltage for sealed lead-acid batteries.
The voltages depend on the number of battery cells and the battery manufacturer. Factory set, they may also be
adjusted by support technicians.
An electronic board continuously measures the battery temperature and automatically adjusts the voltages.
NOTE
In parallel Galaxy PW™ systems, the power drawn by the load is equally shared
between the different units.
Figure 4-5: Normal Operation Indicator Diagram.
1
2
AB
C
D
2
1
4
5
1
Operation
4 — 3
86-133060-00 A00
Summary of Contents for GALAXY PW 100
Page 6: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA vi 86 133060 00 A00...
Page 34: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 2 12 86 133060 00 A00...
Page 78: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA 5 8 86 133060 00 A00...
Page 92: ...This page left blank intentionally Galaxy PWTM UPS 100 to 225 kVA A 14 86 133060 00 A00...
Page 94: ...Galaxy PWTM UPS 100 to 225 kVA 86 133060 00 A00...
Page 96: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA W 4 86 133060 00 A00...
Page 100: ...This page left blank intentionally Galaxy PW UPS 100 to 225kVA G 4 86 133060 00 A00...
Page 102: ......
Page 103: ......