background image

12

8. 

Install  Downdraft  Diverter  and  final  row  of  Side  Walls 

(

Figure 15

). Then place #3 rebar (8 each, 36 inch long) 

vertically through the cells until they reach bottom. Position 

them adjacent to the rebar or all-thread sticking up from the 

hearth.

9.  All components must be level. Mix approx. 2 cu. ft. of Ready-

Mix Concrete. Fill all cells with Ready-Mix Concrete mix. 

Figure 15

Downdraft 

Diverter 

12 inch

rebar or 

all-thread

10. Set the Lintel and Lower Rear Dome as shown in 

Figure 

16

. Check that all is level. If adjustments are needed, use  

shims and fill gaps with an appropriate amount of mortar.

 

Note: 

Although you are cautioned to use MASON-LITE 

mortar sparingly because it does have such holding power, 

you should look over the firebox assembly at the end and fill 

in any gaps, especially joint connections, with the mortar.  

Figure 16

Lintel 

T-Bar

Lower Rear 

Dome

 

Important:

 Adjustments can only be made while the mortar 

is still wet when correcting for squareness and leveling.

11.  Assemble Lower Dome Sides as shown in 

Figure 17

. The 

beveled face lines up with the inward angles of the lintel 

sides. Resulting top surfaces should be level. 

 

Figure 17

Lower Dome Sides (Rating 

Plate faces inside)

 

12. Verify that the smoke dome side, front and rear walls are 

aligning correctly and that the surfaces are smooth and 

uniform.  Make sure connections are covered with an 

adequate  amount  of  mortar.  Remember  that  you  have 

the option of using shims but they must be removed and 

any  holes  filled.  Make  any  adjustments  to  the  appliance 

alignment before continuing to the next step.

13. Assemble Upper Dome and Dome Sides  as shown in 

Figure 18

. Check your assembly here. If things are 

proceeding  as  they  should  be,  the  finished  top  surface 

should be flat and level. 

 

 

Figure 18

Upper Dome Sides

Upper Dome

Front/Rear

14. Finally, set the Dome Top into position. Be sure that it is 

flush in every direction as you place it on the crest of the 

smoke dome wall assembly. After this is done, proceed to  

section on “Installing Damper and Chimney System”

.

Note: 

The chimney  hole on the Dome Top is not centered from 

front  to  back  -  it  should  be  offset  closest  to  the  rear  of  the 

appliance (see 

Figure 

19). 

    

Figure 19

Center of chimney hole is 

offset towards the rear.

10”

12-1/2”

MGFP-39/44/49

Summary of Contents for MASON-LITE MGFP39

Page 1: ...flue meeting the requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this appliance This appliance must be vented vertically through the roof This appliance is not for install...

Page 2: ...mes MFP587C GAS TYPE FOR MANTEL CLEARANCES CONSULT OWNER S MANUAL DO NOT REMOVE THIS LABEL See MFI s installation and operating instructions for this model Contact local building officials about restr...

Page 3: ...anchoring components WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or pe...

Page 4: ...M P N DESCRIPTION QTY 1 MFP39 1 MFP44 1 MFP49 1 HEARTH Left or Right 2 2 MFP39 2 MFP44 2 MFP49 2 REAR WALL 3 3 MFP39 3 MFP44 3 MFP49 3 SIDE WALL 7 3A MFP39 3A MFP44 3A MFP49 3A SIDE WALL with 4 openin...

Page 5: ...ith the minimum firebox dimensions and venting requirements met see table on this page This appliance is designed to burn with yellow flames adequate ventilation is absolutely necessary Table 1 Produc...

Page 6: ...staller is expected to understand each phase completely before going on to subsequent instructions Attention Be advised that all the illustrations in this manual are for general reference only Do not...

Page 7: ...rts and accessories Use of other controls parts and accessories which are not designed for use with MASON LITE gas appliances is prohibited and will void all warranties certifications listings and bui...

Page 8: ...moother and above all safer for everyone concerned At the least reading these procedures will save you time and at the most it will prevent any malfunction that could result in property damage or seri...

Page 9: ...the addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight...

Page 10: ...cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resulting from L D Note that MASON LITE cannot accept...

Page 11: ...pieces 3 8 rebar x 36 long included with unit Eight 8 ea All thread x 12 long with nuts and washers ALL UNITS Three 3 90 lb bags of ready mix concrete with 1 4 or smaller aggregate SURFACE CRACKS The...

Page 12: ...slab Check for surface flatness level if necessary Figure 11 1 2 away from edges 1 2 mortar bead typical Hearth section shown prepared for Right Side position Apply mortar bead to all mating surfaces...

Page 13: ...The beveled face lines up with the inward angles of the lintel sides Resulting top surfaces should be level Figure 17 Lower Dome Sides Rating Plate faces inside 12 Verify that the smoke dome side fro...

Page 14: ...ection of the shelf As a guide figure that a 10 ten inch wide shelf should be 20 twenty inches above the appliance opening 2 Walls That Adjoin Safety codes and all practical outlooks insist that your...

Page 15: ...ey Requirements for Height and Clearance When installed the maximum overall height of the chimney system from bottom of appliance to the top termination chimney is 40 feet The minimum installed height...

Page 16: ...bilizer When installing the stabilizer pull out the support straps with a good amount of tension and hammer to the frame 4 If your offset sections go over 6 six feet in length you will need to give ad...

Page 17: ...rmitted if they do not exceed a 45 inclination The total lengths of the two offsets are not required to meet the 75 allowable rule Example 3 Shows a single offset at 45 of inclination and therefore th...

Page 18: ...water or in a high humidity area the manufacturer recommends a top quality rust proof paint especially formulated for metal Follow the paint manufacturer s directions applying the paint well before y...

Page 19: ...all elements of the appliance and chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first ligh...

Page 20: ...LIGHT THE APPLIANCE WITH THE WALL SWITCH Move the ON REMOTE OFF wall switch to the ON position Figure 41 This transmits a rapid series of sparks at the pilot head and will ignite the gas TO SHUT DOWN...

Page 21: ...rwater Attempted operation may result in fire or explosion resulting in property damage personal injury or loss of life D A appliance screen must be in place when the system is burning Provisions for...

Page 22: ...s may differ depending upon the size of the set purchased Be sure you know the model number and size of your set when ordering replacement or optional parts and accessories Receiver pre assembled into...

Page 23: ...ee Fig 12 3 4 Be sure gas to the appliance is off Remove the adapter connected to the flex connector pre installed on the burner system Attach the adapter to the gas supply stub using a pipe compound...

Page 24: ...ound the switch box Leave the front of the switch box clear for control access 2 Repeat this process for the supplied lava coals on top of the already placed lava granules Note DO NOT place any lava m...

Page 25: ...have developed during shipment Keep some embers for future placement along the front log Ember placement detail Place the front log log 2 as shown Rest the log with its back against the burner assemb...

Page 26: ...25...

Page 27: ...26...

Page 28: ...27...

Page 29: ...28...

Page 30: ...29...

Page 31: ...on a periodic examination and cleaning of the solid fuel burning appliance venting system should be conducted by a qualified professional service technician Any safety screen or guard removed for serv...

Page 32: ...31...

Page 33: ...32...

Page 34: ...33...

Page 35: ...ated 2 Debris around the control Inspect the control and pilot to be sure it is free of any dirt or debris 3 Insects and burner blockage Check the burner ports and the air mixer if present to make sur...

Page 36: ...ld 4 Appliance will not shut OFF a Control Switch lead wires to the valve may be shorted together or on wrong terminals a See wiring diagram previous page System takes 15 20 seconds to complete shutdo...

Page 37: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 38: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 39: ...his warranty makes MFI or any affiliate thereof liable in any respect for any injury or damage to the building or structure in which the appliance has been installed or to the persons or property ther...

Reviews: