background image

 

 

Page 7 of 25 

 

start).  Upon automatic start from this type of switch, the pump will be stopped either automatically after the demand switch 
de-activates and Pump Auto Stop Timer times out, or manually at the Controller.  Terminals #111 and #31 must have a 
jumper installed if a remote Deluge switch is “Enabled” but not to be used.  When the controller is shipped from the factory 
Deluge Valve start is Disabled (System Config screen 121). 

e.

 

AC POWER FAILURE STARTING: 

If this feature has been enabled it can be tested by disconnecting the supervisory 

power 115 V.A.C. to the Controller.  After the preset time delay (which is specified in System Config screen 112), the 
Controller will commence starting of the pump.  The

 "System Fault"

 LED will illuminate and the alarm will sound. 

 

f.

 

NORMAL OPERATION – AUTOMATIC: 

Press 

"Auto"

 mode button on OID.  A green 

"Automatic Mode"

 light will 

illuminate and the pump will automatically start upon drop in pressure or operation of other start switches.  If the Auto Stop 
Timer is disabled (Manual Stop) the pump must be turned off at the Controller.  When the Auto Stop Timer is enabled, upon 
termination of the demand signal, the pump will run for the length of time left on the Auto Stop Timer and then will stop 
automatically.

 

g.

 

AN ADJUSTABLE SEQUENTIAL START TIMER IS SUPPLIED FOR MULTIPLE PUMP INSTALLATION: 

Normally, the leading pump Controller will not have a delay timer and will commence starting of the pump immediately 
upon operation of a demand signal (other than Power Failure which is time delayed).  The subsequent Controllers will have a 
time delay which is adjustable from 0 to 999 seconds.  Each time delay should be set with progressively longer times on each 
subsequent pump.  The recommended time interval is ten (10) to fifteen (15) seconds. This may be extended or shortened as 
required by the local authorities having jurisdiction.  

h.

 

PUMP ROOM ALARMS: 

Field terminals may be provided for various inputs from pump room alarms.  These alarms 

include:  Low Pump Room Temperature, Reservoir Low, Reservoir Empty, Low Suction Pressure, Relief Valve Discharge 
and/or Flow Meter On etc.  A maximum of twelve (12) (or nine (9) if a transfer switch is supplied), pump room alarms is 
available. Each auxiliary alarm is configurable so that the alarm horn may or may not sound and the light will come on when 
the alarm sensor contacts close.  These pump room alarms can be silenced with the “Silence” push button on the OID if they 
have been configured as silenceable. 

Summary of Contents for MP430 Series

Page 1: ...Laboratories and approved by Factory Mutual Research Corporation Sizes range from 15 to 700 horsepower 200 to 600 volts 50 Hz These controllers are for use on Reduced Voltage type installations Only t...

Page 2: ...es by 20 character display with large character backlit Liquid Crystal Display LCD capable of being read in both direct sunlight or dark lighting conditions 12 pushbuttons for easy screen navigation s...

Page 3: ...the following data recorded with the event alarm providing an accurate record of events Time and Date of Event or Alarm System Pressure Descriptive Text Message of the Event Alarm Motor Running Statu...

Page 4: ...t status LED s to provide visual indication of each discrete input s or output s on off status One RS232 Serial Port One USB 1 0 Port One RS485 Serial Port All wiring terminals on PCB s shall be remov...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ...0 Electric Motor Driven Fire Pump Controllers TABLE OF CONTENTS PART I General Information PAGE 3 PART II Functions PAGE 3 PART III Operation of the Controller PAGE 4 PART IV Installation Test Procedu...

Page 10: ...Page 2 of 25 THIS PAGE IS BLANK...

Page 11: ...provided for Transfer Switch in Normal Transfer Switch in Emergency and Emergency Iso Sw Open In addition the mode buttons have LED s on the button indicating Auto Manual Test or Off mode 12 additiona...

Page 12: ...pressure if the Solenoid Drain Valve Option Screen 108 is selected If the Solenoid Drain Valve Option is set to NO the unit will start automatically similar to the Deluge Valve switch start feature Fa...

Page 13: ...up for the ramp stop option Screen 106 the motor will ramp down in speed over a fixed time delay Screen 107 until it stops Note When using the emergency manual start handle the soft start unit may di...

Page 14: ...eaker Shunt Trip Out 03 Start Contactor relay if applicable Out 04 Run Contactor relay Out 05 Start signal to Soft Start Model MP700 only Out 06 Power to Soft Start Model MP700 only In 01 Emergency St...

Page 15: ...gnal the pump will run for the length of time left on the Auto Stop Timer and then will stop automatically g AN ADJUSTABLE SEQUENTIAL START TIMER IS SUPPLIED FOR MULTIPLE PUMP INSTALLATION Normally th...

Page 16: ...Mode Change The operational mode that the controller is in can be changed by pressing the AUTO MANUAL or OFF buttons An LED will illuminate on the appropriate button indicating the mode of operation t...

Page 17: ...arm Occurred 10 16 04 06 49 03 3 EVENT LOG Supvr Power Failure Alarm Cleared 10 16 04 07 09 48 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH PRESSURE LOG 10 16 04 17 52 30 112 psi Skip Rate EA...

Page 18: ...SYSTEM SETPOINTS Pump Automatic Stop Enabled Yes 105 SYSTEM SETPOINTS Pump Minimum Run Time 30 minutes 30 99 109 SYSTEM SETPOINTS Automatic Weekly Test Run Yes 101 SYSTEM SETPOINTS Pump Start Pressur...

Page 19: ...ER PREFERENCES No Load Amps of FLA 5 0 99 317 TECH SCREENS Motor Run of FLA 20 0 99 319 TECH SCREENS Overload Alarm of FLA 125 100 199 320 TECH SCREENS Overload Alarm Time Delay 3 sec 0 99 322 TECH SC...

Page 20: ...r descriptions on the functionality of each set point 1 SYSTEM STATUS B1 PRES STRT AB 460V 110 100 BC 461V psi psi AC 460V SYSTEM LOGS 1 Alarm Log 2 Event Log 3 Pressure Log 1 CONFIG 1 SYSTEM SETPOINT...

Page 21: ...s 1 ALARM LOG Pump Failed To Start Alarm Occurred 10 16 04 07 32 15 1 EVENT LOG System in Off Mode Occurred 10 16 04 13 15 15 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH 1 ALARM DETAILS Pump...

Page 22: ...ou have connected to Typical Event Alarm Log Message Printout 1 EVENT LOG Superv Power Failure Alarm Occurred On 10 16 04 07 32 15 PRINT OPTIONS 1 PRINT THIS EVENT 2 PRINT EVENT RANGE 10 BEFORE 10 AFT...

Page 23: ...vigate to the configuration set point screen that contains the value that needs to be changed 2 Press CHANGE ENTER If a password has not been entered for a while the ENTER PASSWORD screen will be disp...

Page 24: ...g all set points only Aux 01 User Programs 501 through 515 will be printed To print any of the remaining eleven aux alarm settings press PRINT when inside the appropriate Aux alarm and select 2 for 2...

Page 25: ...per NFPA 20 Only active if 104 above is set to Enabled 106 SYSTEM SETPOINTS Ramp Stop Option Time M700 Yes When set to Yes and the controller is set for Model MP700 the controller will stop the pump...

Page 26: ...rt Time Delay 1 minutes 0 999 The amount of time the controller will delay starting of the pump on loss of the 120VAC Supervisory power source 118 SYSTEM SETPOINTS Pressure Transducer Failure Pump Sta...

Page 27: ...TS Deluge Valve Pump Start No If enabled this setting activates the logic to monitor an optional deluge valve dry contact opening ie normally closed contact that opens to start pump that will start th...

Page 28: ...ENCES Time Between Pressure Log Samples 15 seconds 15 999 The frequency at which system pressure is automatically logged Normally set to 15 seconds Lower values will increase the number of logged pres...

Page 29: ...e before the alarm condition is activated 218 USER PREFERENCES No Load Amps Of FLA 10 0 99 The of motor full load current at which or below that will cause an event to be logged indicating a No Load M...

Page 30: ...System was placed in Manual mode Auto Test Start Occurred An automatic pump test sequence was started while in Auto mode by either the weekly program clock function or a user pressing the TEST button...

Page 31: ...or Ajar List of possible internal variables used as inputs for aux alarm user programs 30 Pump Running 31 Power Available 32 Phase Reversal 33 Motor Overload 34 Remote Start 35 Local Start 36 Pump On...

Page 32: ...r tear the end off against the paper tear bar and carefully pull the remaining paper backwards from the rear of the mechanism mounting chassis until the free end emerges Press the paper roll retaining...

Page 33: ...ridge ensuring that the paper lies between the ribbon and the steel printer platen Check that the ribbon cartridge spindle is correctly seated over the printer ribbon drive shaft and snap the cartridg...

Reviews: