318  TECH SCREENS   

Use Motor Current

for Pump Running Sig

[Yes]

316  TECH SCREENS   
Single Phase Loss

 Time Delay 

[5]seconds      0-99

220 USER PREFERENCES
LCD Back Light Mode

        0=Always on

[0]]    1=Power Save

221 USER PREFERENCES
Language Select

[English]

222 USER PREFERENCES
Change User Password
Level 1

[****]

120 SYSTEM SETPOINTS

  Shutdown On Low
  Intake Trip Time

[  0]seconds   0-999

119 SYSTEM SETPOINTS

  Shutdown On Low

Intake Pressure/Lvl

[No ]

118 SYSTEM SETPOINTS
Pressure Transducer
Failure Pump Start

[ No] 

117 SYSTEM SETPOINTS
Supvervisory Power 
Fail Start Dly Time

[  1]minutes  0-500

116 SYSTEM SETPOINTS

 Supervisory Power

Failure Startup

[Yes]

ANALOG INPUT COUNTS 
 649 1176 1221    0 
   0    0    0    0 
     0          0   

415 ANALOG SIGNALS  
Phase BC Voltage

Offset:    

[6.52430]

121 SYSTEM SETPOINTS

Low Intake Shutdown

     Auto Reset

[ No]

124 SYSTEM SETPOINTS

    Deluge Valve
    Pump Start

[No]

123 SYSTEM SETPOINTS

  Pressure Switch
   Pump Start

[No ]

122 SYSTEM SETPOINTS

Low Intake Shutdown

  Auto Reset Time

[  0]seconds   0-999

216 USER PREFERENCES
Low Discharge 

Alarm Pressure

[100]         0-999

217 USER PREFERENCES
Low Discharge Alarm 
Time Delay

[ 8]sec         0-99

219 USER PREFERENCES

No Load Time 

Time Delay

[ 8]sec         0-99

218 USER PREFERENCES

No Load Amps % 
  of FLA

[  5]         0-99

317  TECH SCREENS   

Motor Run % of

FLA

[20]%      0-99

319  TECH SCREENS   

Overload Alarm
% of FLA

[125]%      100-199

320  TECH SCREENS   

Overload Alarm
Time Delay

[3]sec       0-99

322  TECH SCREENS   

Motor Run Amps

Time Delay

[5]sec       0-99

323  TECH SCREENS   

Motor Start

Time Delay

[10]sec       0-99

324  TECH SCREENS   

Under Frequency
% of Nominal

[25]         0-99

325  TECH SCREENS   

Under Frequency 
Time Delay

[5]sec       0-99

326  TECH SCREENS   

Over Frequency
% of Nominal

[25]%       0-999

321  TECH SCREENS   
Start on Single
Phase Loss

[Yes]

327  TECH SCREENS   

Over Frequency
Time Delay

[5]sec        0-99

328  TECH SCREENS   

Alarm log 31/2
Event log 50/ 4

Pr. log    0/29333

329  TECH SCREENS   
System Commissioned
Date

[00/00/00]   

330  TECH SCREENS   
Change Tech Password

[******]

331  TECH SCREENS   
Password Logout
Time

[5]min      1-15

416 ANALOG SIGNALS  
Phase AC Voltage    
Slope:           

[0.729750]         

417 ANALOG SIGNALS  
Phase AC Voltage

Offset:      

[6.52430] 

418 ANALOG SIGNALS  

Minimum Amps
      

[10]         0-9999

421 ANALOG SIGNALS  
Phase B Amps    
Slope:             

[ 2.9635]         

424 ANALOG SIGNALS  
Phase C Amps

Offset:    

[36.9270]

423 ANALOG SIGNALS  
Phase C Amps    
Slope:             

[ 2.9635]         

422 ANALOG SIGNALS  
Phase B Amps

Offset:    

[36.9270]

420 ANALOG SIGNALS  
Phase A Amps    

Offset:            

[36.9270]

419 ANALOG SIGNALS  
Phase A Amps
Slope:     

[ 2.9635]

425 ANALOG SIGNALS  
Set Volts/Amps Slope

Offset to Fact 
Dflt[Yes]

223 USER PREFERENCES
Reversed Phase

 order (1-3-2)

[No]

Daughter board
counts 

 649 1176 1221    0 
   0    0    0    0    

 

Summary of Contents for MP430 Series

Page 1: ...Laboratories and approved by Factory Mutual Research Corporation Sizes range from 15 to 700 horsepower 200 to 600 volts 50 Hz These controllers are for use on Reduced Voltage type installations Only t...

Page 2: ...es by 20 character display with large character backlit Liquid Crystal Display LCD capable of being read in both direct sunlight or dark lighting conditions 12 pushbuttons for easy screen navigation s...

Page 3: ...the following data recorded with the event alarm providing an accurate record of events Time and Date of Event or Alarm System Pressure Descriptive Text Message of the Event Alarm Motor Running Statu...

Page 4: ...t status LED s to provide visual indication of each discrete input s or output s on off status One RS232 Serial Port One USB 1 0 Port One RS485 Serial Port All wiring terminals on PCB s shall be remov...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ...0 Electric Motor Driven Fire Pump Controllers TABLE OF CONTENTS PART I General Information PAGE 3 PART II Functions PAGE 3 PART III Operation of the Controller PAGE 4 PART IV Installation Test Procedu...

Page 10: ...Page 2 of 25 THIS PAGE IS BLANK...

Page 11: ...provided for Transfer Switch in Normal Transfer Switch in Emergency and Emergency Iso Sw Open In addition the mode buttons have LED s on the button indicating Auto Manual Test or Off mode 12 additiona...

Page 12: ...pressure if the Solenoid Drain Valve Option Screen 108 is selected If the Solenoid Drain Valve Option is set to NO the unit will start automatically similar to the Deluge Valve switch start feature Fa...

Page 13: ...up for the ramp stop option Screen 106 the motor will ramp down in speed over a fixed time delay Screen 107 until it stops Note When using the emergency manual start handle the soft start unit may di...

Page 14: ...eaker Shunt Trip Out 03 Start Contactor relay if applicable Out 04 Run Contactor relay Out 05 Start signal to Soft Start Model MP700 only Out 06 Power to Soft Start Model MP700 only In 01 Emergency St...

Page 15: ...gnal the pump will run for the length of time left on the Auto Stop Timer and then will stop automatically g AN ADJUSTABLE SEQUENTIAL START TIMER IS SUPPLIED FOR MULTIPLE PUMP INSTALLATION Normally th...

Page 16: ...Mode Change The operational mode that the controller is in can be changed by pressing the AUTO MANUAL or OFF buttons An LED will illuminate on the appropriate button indicating the mode of operation t...

Page 17: ...arm Occurred 10 16 04 06 49 03 3 EVENT LOG Supvr Power Failure Alarm Cleared 10 16 04 07 09 48 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH PRESSURE LOG 10 16 04 17 52 30 112 psi Skip Rate EA...

Page 18: ...SYSTEM SETPOINTS Pump Automatic Stop Enabled Yes 105 SYSTEM SETPOINTS Pump Minimum Run Time 30 minutes 30 99 109 SYSTEM SETPOINTS Automatic Weekly Test Run Yes 101 SYSTEM SETPOINTS Pump Start Pressur...

Page 19: ...ER PREFERENCES No Load Amps of FLA 5 0 99 317 TECH SCREENS Motor Run of FLA 20 0 99 319 TECH SCREENS Overload Alarm of FLA 125 100 199 320 TECH SCREENS Overload Alarm Time Delay 3 sec 0 99 322 TECH SC...

Page 20: ...r descriptions on the functionality of each set point 1 SYSTEM STATUS B1 PRES STRT AB 460V 110 100 BC 461V psi psi AC 460V SYSTEM LOGS 1 Alarm Log 2 Event Log 3 Pressure Log 1 CONFIG 1 SYSTEM SETPOINT...

Page 21: ...s 1 ALARM LOG Pump Failed To Start Alarm Occurred 10 16 04 07 32 15 1 EVENT LOG System in Off Mode Occurred 10 16 04 13 15 15 PRESSURE LOG 10 16 04 17 52 45 112 psi Skip Rate EACH 1 ALARM DETAILS Pump...

Page 22: ...ou have connected to Typical Event Alarm Log Message Printout 1 EVENT LOG Superv Power Failure Alarm Occurred On 10 16 04 07 32 15 PRINT OPTIONS 1 PRINT THIS EVENT 2 PRINT EVENT RANGE 10 BEFORE 10 AFT...

Page 23: ...vigate to the configuration set point screen that contains the value that needs to be changed 2 Press CHANGE ENTER If a password has not been entered for a while the ENTER PASSWORD screen will be disp...

Page 24: ...g all set points only Aux 01 User Programs 501 through 515 will be printed To print any of the remaining eleven aux alarm settings press PRINT when inside the appropriate Aux alarm and select 2 for 2...

Page 25: ...per NFPA 20 Only active if 104 above is set to Enabled 106 SYSTEM SETPOINTS Ramp Stop Option Time M700 Yes When set to Yes and the controller is set for Model MP700 the controller will stop the pump...

Page 26: ...rt Time Delay 1 minutes 0 999 The amount of time the controller will delay starting of the pump on loss of the 120VAC Supervisory power source 118 SYSTEM SETPOINTS Pressure Transducer Failure Pump Sta...

Page 27: ...TS Deluge Valve Pump Start No If enabled this setting activates the logic to monitor an optional deluge valve dry contact opening ie normally closed contact that opens to start pump that will start th...

Page 28: ...ENCES Time Between Pressure Log Samples 15 seconds 15 999 The frequency at which system pressure is automatically logged Normally set to 15 seconds Lower values will increase the number of logged pres...

Page 29: ...e before the alarm condition is activated 218 USER PREFERENCES No Load Amps Of FLA 10 0 99 The of motor full load current at which or below that will cause an event to be logged indicating a No Load M...

Page 30: ...System was placed in Manual mode Auto Test Start Occurred An automatic pump test sequence was started while in Auto mode by either the weekly program clock function or a user pressing the TEST button...

Page 31: ...or Ajar List of possible internal variables used as inputs for aux alarm user programs 30 Pump Running 31 Power Available 32 Phase Reversal 33 Motor Overload 34 Remote Start 35 Local Start 36 Pump On...

Page 32: ...r tear the end off against the paper tear bar and carefully pull the remaining paper backwards from the rear of the mechanism mounting chassis until the free end emerges Press the paper roll retaining...

Page 33: ...ridge ensuring that the paper lies between the ribbon and the steel printer platen Check that the ribbon cartridge spindle is correctly seated over the printer ribbon drive shaft and snap the cartridg...

Reviews: