MI 3108 EurotestPV
Instrument operation
28
Selective
RCDs
(time-delayed)
t
> 1999
ms
130 ms < t
< 500
ms
60 ms < t
< 200
ms
50 ms < t
< 150
ms
Trip-out times according to AS/NZS 3017
**)
:
½
I
N
*)
I
N
2
I
N
5
I
N
RCD type
I
N
[mA]
t
t
t
t
Note
I
10
> 999 ms
40 ms
40 ms
40 ms
Maximum break time
II
> 10
30
300 ms
150 ms
40 ms
III
> 30
300 ms
150 ms
40 ms
IV
S
> 30
> 999 ms
500 ms
200 ms
150 ms
130 ms
60 ms
50 ms
Minimum non-actuating time
*)
Minimum test period for current of ½
I
N
, RCD shall not trip-out.
**)
Test current and measurement accuracy correspond to AS/NZS 3017 requirements.
Maximum test times related to selected test current for general (non-delayed) RCD
Standard
½
I
N
I
N
2
I
N
5
I
N
EN 61008 / EN 61009
300 ms
300 ms
150 ms
40 ms
EN 60364-4-41
1000 ms
1000 ms
150 ms
40 ms
BS 7671
2000 ms
300 ms
150 ms
40 ms
AS/NZS 3017 (I, II, III)
1000 ms
1000 ms
150 ms
40 ms
Maximum test times related to selected test current for selective (time-delayed) RCD
Standard
½
I
N
I
N
2
I
N
5
I
N
EN 61008 / EN 61009
500 ms
500 ms
200 ms
150 ms
EN 60364-4-41
1000 ms
1000 ms
200 ms
150 ms
BS 7671
2000 ms
500 ms
200 ms
150 ms
AS/NZS 3017 (IV)
1000 ms
1000 ms
200 ms
150 ms
4.4.5 Z factor
In this menu Z correction factor for limit of
maximum Line / Loop impedance can be
set.
Figure 4.9: Selection of Z factor
Keys:
UP / DOWN
Sets Z factor value.
TEST
Confirms Z factor value.
ESC
Exits back to settings menu.
Function selectors
Exits back to main menu without changes.
Maximum impedance in the supply system is important for selection or verification of
protective circuit breakers (fuses, over-current breaking devices, RCDs).