MI 3110 EurotestIM
Appendix A
– Fuse table
56
Fuse type D
Fuse type BS 88-3 (system C)
Rated
current
(A)
Disconnection time [s]
Rated
current
(A)
Disconnection time [s]
0.4
5
0.4
5
Max. loop impedance (
)
Max. loop impedance (
)
6
1,536
1,536
5
8,36
12,264
10
0,92
0,92
16
1,936
3,288
16
0,576
0,576
20
1,632
2,704
20
0,456
0,456
32
0,768
1,312
25
0,368
0,368
45
0,832
32
0,288
0,288
63
0,576
40
0,232
0,232
80
0,424
50
0,184
0,184
100
0,32
63
0,144
0,144
80
0,112
0,112
100
0,088
0,088
125
0,072
0,072
Fuse type BS 88-2 (systems E and G)
Fuse type BS 1362
Rated
current
(A)
Disconnection time [s]
Rated
current
(A)
Disconnection time [s]
0.4
5
0.4
5
Max. loop impedance (
)
Max. loop impedance (
)
6
6,568
10,24
3
13,12
18,56
10
3,912
5,752
13
1,936
3,064
16
2,048
3,344
Fuse type BS 3036
20
1,416
2,36
25
1,08
1,84
Rated
current
(A)
Disconnection time [s]
32
0,832
1,472
0.4
5
40
1,08
Max. loop impedance (
)
50
0,832
5
7,664
14,16
63
0,656
15
2,04
4,28
80
0,456
20
1,416
3,064
100
0,368
30
0,872
2,112
125
0,272
45
1,272
160
0,224
60
0,896
200
0,152
100
0,424
All impedances are scaled with factor 0.8.