34/78
meteocontrol Power Control 03082012 - en
7.1
Active power procedures
7.1.1
P(DI)
With this procedure, the active power P is used as the control value.
The DI requirement is provided by the energy supplier as a digital input
signal, e.g. digital ripple control receiver and connected to the digital inputs of
the PCU.
Note:
Only individual outputs of the ripple control receiver may be
assigned. Bit samples (DI 1,2,4 = H‘07 for assignment of
requirement value) are not permitted.
Feedback is provided via the digital outputs of the PCU.
Fig. 24: Active power procedure control P(DI)
Note:
The areas highlighted in red in the Fig. shown below
illustrate the settings fields relevant for the active power
procedure P(DI).
Input field
Meaning
Active power procedure
Indicates the active power procedure P(DI)
selected