Metel 1-988-220 Quick Installation Manual Download Page 21

Quick Installation Manual REV:202204

2G-2S.0.3.F-BOX-PoE 

Industrial PoE+ Managed Switches

www.metel.eu                                 21/23

  

                              www.iplog.eu

  P1 – P3: Fast ethernet ports 10 / 100Mbps. The production 

firmware supports PoE according to IEEE 802.3af / at. 
The maximum power consumption from one port is 
30W. The maximum power of PoE over all ports is 
90W. Performance on individual ports can be set in 
the Simuland v4 application.

FE ports are protected by overvoltage protection 150A (8/20μs).

 

BUS1, BUS2:
2 serial buses 
RS485.Overvoltage
protection 30A 
(8/20μs).

4. Insert Optical Module

Any SFP module complying with MSA requirements
(agreement of SFP modules manufacturers) can be
inserted into the SFP slot. For modules with duplex
transmission over one fiber (wavelength multiplex) we
must ensure that the optical modules are connected
correctly to each other. That means that e.g. for WDM

modules METEL can interconnect W4 with W5. We
can’t interconnect W4 with W4 or W5 with W5.

Note:

For the correct functioning of LAN-RING.v1 and v2 it is
necessary to observe the correct connection to the GBIC

modules. W4 module must be plugged into the slot
MiniGBIC-G1 and module labeled W5 into the slot
labeled MiniGBIC-G2.

W5

Tx:1550nm
Rx:1310nm

W4

Tx:1310nm
Rx:1550nm

~

V1

+V2

~

V1/+V1

+V2

GND

5

4

3

2

1

Galvanically Separated Cover

Lightning Arrestors

FE 1 … FE 3

P

1

P

2

P

3

U

SB

IN

2

|

IN

1

O

U

T

G

2

R

IN

G

G

1

P

W
R

miniGBIC-G2 miniGBIC-G1

G

N

D

B

-

A

+

G

N

D

B

-

A

+

G

N

D

IN

2

IN

1

N

.O

.

C

O

M

N

.C

.

   OUT

BUS1

BUS2

CLASS 1 LASER
PRODUCT!

www.metel.eu
2G-2S.0.3.F-BOX #1-988-220

B

2

|

B

1

LAN-RING Ethernet Switch

~

V

1

+

V

2

~

V

1

/+

V

1

+

V

2

G

N

D

5

4

3

2

1

USB: 
local USB 
management

See page 22 for 
connection 
information.

SFP SLOTS miniGBIC
100/1000BASE-X

Redundant DC Power Supply

Main Input +10 to +60V DC     

Redundant Input +10 to +60V DC     

Note: Terminals 2 and 4 are connected.

AC Power

Input 10 to 30V AC

1. Mounting

Install  the  switch  on  a  level  surface  or  DIN35.  The 
necessary holders are included.  

2. Connect the Power 

According to the pictures below, connect the power
supply in the range of 10-60VDC or 10-30VAC. Connection
of supply is indicated by LED PWR switching on. 

 

See  page  22  for  important  information  regarding 
the el. safety of the PoE power supply.

3. Grounding of Overvoltage Protections

Connect  the  protection  with  the  green-yellow 
wire, which is part of the switch, to an earth point 
with a resistance of up to 10Ω. 

The  switch  cover  is  galvanically  separated  from 
the electronics on the PCB, which allows its use in 
systems  with  a  grounded  (+)  or  (-)  pole.  A 
lightning arrester is connected  between the  GND 
terminal and the cover.

IN1, IN2
Programmable digital/alarm inputs for 
connection of contact switches, tampers, 
PIR sensors,...Inputs are protected with 

overvoltage protection 30A (8/20μs).

OUT
Relay with change-over contact. Output 
is protected with resetable current 
protection.

5
4
3
2
1

  +

 

  +

 

  

  GND

Source

  +

  GND

Source

5
4
3
2
1

5
4
3
2
1

 

 

 GND

Source

Summary of Contents for 1-988-220

Page 1: ...hernet Port with PoE IEEE 802 3af at max 30W per Port vTotal PoE Power Over All Ports is 90W v2x RS485 Modbus RTU Buses v2x Digital Alarm Inputs v1x Programmable Relay Output v2 Independent Power Inputs vRedundant Topology LAN RING RSTP vEvent Management with Support HTTP ONVIF Client E mail IP Watchdogs ETH Events TCP Modbus DIO Balanced Loops vVisualization Software Support vEncrypted Management...

Page 2: ...n of PoE over all ports is 90W 2x RS485 Modbus RTU Buses The switches are equipped with two RS485 buses enabling the connection of Modbus RTU IO modules and sensors selected types of I HAS systems and other devices The transmission of system buses of I HAS systems is certified according to EN50131 1 Further info page 8 9 2x Digital Alarm Inputs Digital alarm inputs are mainly used for connecting b...

Page 3: ...0 30 10 60 VDC AC With PoE up to 15 4W 48 57 48 57 VDC Weight 0 65 kg Relay Output Type of Contact 1x Change Over Analog 0 30kΩ for Balanced Loops Overvoltage Protection 30 A 8 20μs Speed Max 57 6 kbps RS485 Number 2 Digital inputs Number 2 Mode Digital NC NO The producer retains the right to change any technical parameters without previous written or published notification Certification CE TUV Te...

Page 4: ...G 2S 0 3 F 2G 2S 0 3 F PoE SNMP MODBUS VLAN RSTP ONVIF 802 1X Dimensions of 2G 2S 0 3 F universality REV 201406 Default 201504 Added Installation GBIC Modules 201904 Design change added 802 1X protocol galvanically separated cover from the electronics 202204 Change PoE circuit ...

Page 5: ...ommunication analysis including fully automatic detection of network topology with display of optical and metallic connections amount of transmitted data in Mbps in connections number of dropped packets on ports PoE status power status input outputs ports status Processor Intel Core 2 DUO 2GHz AMD X2 2GHz or faster LIST OF SUPPORTED DEVICES BB x x x 22 200M 1 0 4 E W4 200M 1 0 4 E W4 PoE 200M 1 0 ...

Page 6: ...n which controls the ring In the case of a failure the MASTER function moves to the switch next to the failure From the origin of the problem to the time of its removal only one interruption occurs of up to maximum of 30ms Initial State Failure Failure Resolution Final State The switchover time to the back up line is for LAN RING protocols slightly dependent on the number of switches connected in ...

Page 7: ...TART POE OUTPUTS Restarts PoE with IP Watchdog EMAIL OUTPUTS Sends E mails ONVIF OUTPUTS Controls Cameras HTTP OUTPUTS Sends HTTP Commands to CAM NVR PLC IP WATCHDOGS INPUTS Monitors IP devices OPTICAL RINGS INPUTS Monitors Optical RINGs States FE GE FO PORTS INPUTS and OUTPUTS Monitors Port States Port Control Nastavení výstupu Automatic Actions LAN RING Switch Loading of the Switch Input Process...

Page 8: ...signed to outgoing packets VLAN ID VLAN tag for sending and receiving packets Transmit address 1 to 5 multicast address for sending packets Application note I O transfer between switches Event Management ETH DIGITAL DIGITAL DIGITAL inputs allow you to set automatic actions with digital inputs of switches IN1 and IN2 DIGITAL MODE supported modes Close event is triggered by closing the input connect...

Page 9: ...ent immediately State change Response to state change only Value direct The current value of the balanced loop is sent every 3 seconds When the value of the balanced loop changes the information is sent immediately Value change The information is sent when the value of the balanced loop changes ACTIVE resistance ranges defined in Extension Input Alarm In total 8 ranges up to a maximum of 30 000 Oh...

Page 10: ...f SNMP rings which also contains SNMP TRAP permissions Event Management LAN RING TCP MIOS EXP C TCP The switch can listen on the specified TCP port set in the Extensions TCP menu If a device on the network sends a notification to the switch s IP address and the specified TCP port the switch can respond to it with the created automatic action MODE supported modes Matches the pattern entered must ma...

Page 11: ...DE Normal port active ready Down port off Normal Down port on off Down Normal port off on Example The P2 port on the switch is controlled by ETH Event ID 15 The METEL SWITCH MIB file is available for monitoring FE GE FO ports via the SNMP protocol which also contains SNMP TRAP permissions Event Management SWITCH BUS BUS RS485 bus monitoring Active the event starts with the start of activity on the...

Page 12: ...er device writes to COIL register No 3 on the switch and thus turns on off port No 1 on the switch MODBUS MASTER The correct settings of the connected Modbus devices are described in the application note titled MODBUS configuration where the entire settings are described including automatic actions In automatic action with Modbus Master on the side the switch is in the role of Modbus Master device...

Page 13: ...egisters to be used and creates a link for the Slots menu Each switch supports the configuration of 64 different registers and their combinations Register 1 64 The registry label is stored only in the SIMULand v4 project Type Register type and its specifications Count The number of registers to be read starts at the Register address All other expected responses cannot exceed the allowed length 256...

Page 14: ... Negation output negation Enable manual output enable relay control from Simuland Output state checked activated in combination with enable manual output the relay will be closed Pulse duration s length of closing opening in pulse mode The METEL COMIO DIO MIB file MIB is available for SNMP relay control Camera Controls up to 8 Onvif cameras or HTTP commands CHANNEL camera number set in the Extensi...

Page 15: ... of 8 IP cameras Settings IP camera specifications in the Extension IP watchdog menu IP address IP address of the camera Retry count number of arp unsuccessful successful queries before the set action is run Restart PoE restart PoE power supply Restart PoE timeout s time for which the PoE power supply will be switched off ensuring the discharge of capacitors in the PoE device If the IP camera is n...

Page 16: ...SET I HAS Fides GALAXY O O P P I HAS Honeywell MODBUS P P P P MODBUS ASCII RTU RS485 P P P P Typically 4 5ms delay between RS ports Event Management Serial Bus BUS Setting the operating mode of RS485 buses Mode supported protocol RS485 general RS485 communication with Modbus RTU support Asset for I HAS systems Asset Galaxy for Galaxy Dimension I HAS systems Other items only apply in RS485 mode Mod...

Page 17: ...ution for Data Collection Control and Visualization of Objects Another option for data processing from Modbus devices is PLC IPLOG It can also execute a program written in FBD LD ST or IL languages according to IEC 61131 3 and visualize the values in the IFTER EQU software PARAMETRY PLC SWITCH MODBUS RTU IPLOG GAMA LAN RING F G Bitrate 115 2 19 2 kbps 57 6 19 2 kbps Distance Max 100 1 200 m Max 10...

Page 18: ...ents for secure communication according to EN 62676 1 2 If switches are used for data transmission of alarm systems they are also subject to the EN50131 1 standard In this case different VLANs and priorities QoS must be used for each service We recommend assigning the highest priority QoS to the I HAS system and the second highest to device management FAQ for Using LAN RING as a I HAS Transmission...

Page 19: ...tches support the LLDP protocol to promote their identity and capabilities among neighboring devices on the LAN We use this protocol to draw the topology in the SIMULandv4 software SNMP Simple Network Management Protocol Switches are supported by a variety of monitoring and visualization softwares For security reasons exclusively encrypted SNMP v3 and methods are used for communication with these ...

Page 20: ...s support the creation of virtual private networks and the prioritization of various types of traffic SNTP Simple Network Time Protocol The switches support the SNTP time protocol and use it for example when logging events to the SD card of the switch SMTP Simple Mail Transfer Protocol In the Automatic Actions of event management it is possible to set the sending of e mails on port 25 RSTP Rapid S...

Page 21: ...2 P3 USB IN2 IN1 OUT G2 RING G1 PWR miniGBIC G2 miniGBIC G1 GND B A GND B A GND IN2 IN1 N O COM N C OUT BUS1 BUS2 CLASS 1 LASER PRODUCT www metel eu 2G 2S 0 3 F BOX 1 988 220 B2 B1 LAN RING Ethernet Switch V1 V2 V1 V1 V2 GND 5 4 3 2 1 USB local USB management See page 22 for connection information SFP SLOTS miniGBIC 100 1000BASE X Redundant DC Power Supply Main Input 10 to 60V DC Redundant Input 1...

Page 22: ...I RCD 30mA L N PE GND With an isolated connection the PC can be connected directly without additional separation Connection with Grounded or Power Pole In PoE systems with a directly grounded or pole it is necessary to place increased emphasis on el safety Especially in cases where PoE cables interfere with outdoor or humid environments contact of live parts with a potential against the ground can...

Page 23: ...ol is off RING v2 RING 1x ON to OFF the switch is MASTER and the circle is closed 4x ON to OFF the switch is MASTER the circle is not closed 1x flashing the switch is SLAVE and the circle is closed 2x flashing the switch is SLAVE the circle is not closed OFF LAN RING protocol is off miniGBIC G1 G2 lights connected optical fiber with the other side flashing the communication PoE P1 P3 lights green ...