SWITCH
The switch item is available as an input and as an output during setup.
SWITCH as Input
SWITCH inputs allow you to set automatic actions where the ports of the switch are used as inputs.
MODE
Link Up / Link down
- the event is triggered if the port becomes active/inactive
Direct
- the port status is sent every 3 seconds. When a change is made, the change is sent immediately
Change
- the event is triggered by connecting or disconnecting the port
Example:
In the case port 3 becomes inactive, this information is stored on the switch's internal SD card.
SWITCH as Output
Allows to control FE/GE/FO ports of the switch by external signals.
MODE
Normal
- port active, ready
Down
- port off
Normal/Down
- port on/off
Down/Normal
- port off/on
Example:
The P2 port on the switch is controlled by ETH Event ID#15.
&
The METEL-SWITCH-MIB file is available for monitoring FE, GE, FO ports via the SNMP protocol,
which also contains SNMP TRAP permissions.
Event Management - SWITCH, BUS
BUS
RS485 bus monitoring.
Active
-
the event starts with the start of activity on the RS485 bus
Inactive
-
the event starts with the end of the activity on the RS485 bus
Direct
– the event is sent every 3 seconds. When an activity changes, the change is sent immediately
Change
- the event is triggered with each change of activity on the bus
Example:
In case
when data reception on the BUS2 is interrupted, the log is written to the SD card of the
switch.
&
The METEL-COMIO-BUS-MIB file is available for SNMP bus monitoring, which also contains SNMP
TRAP permissions.