METAL-FACH
Heating Technology
19
The boiler should be placed on a heat insulating non-flammable base, which on each side of the boiler should
be larger than the base of the boiler by 2 cm. If the boiler is located in a cellar, it is recommended that it is
placed on a foundation of at least 5 cm. The strength of the foundation as well as the fire protection conditions
are key guidelines when placing the boiler in the right location, these include:
20 cm safe distance from flammable materials,
40 cm for flammable materials of flammability grade C3,
40 cm if the flammability degree is not known.
Degree of combustibility of building masses and products
Building materials and products
A - Non-flammable
Sandstone, concrete, bricks, fireproofing plaster,
mortar, ceramic tiles, granite
B - Hardly flammable
Wood and cement boards, fibreglass, mineral
insulation
C1 - Sparingly combustible
Beech wood, oak wood, plywood
C2 - Moderately flammable
Pine, larch and spruce wood cork, sawn timber
boards, rubber floor coverings
C3 - Easily burning
Asphalt plywood, celluloid, polyurethane,
polystyrene, polyethylene, plastic, PVC
Boiler connection to the heating system
(Installer)
Boiler connection to the central heating system should be performed by a firm authorized by the manufacturer,
and the fact of a proper connection should be confirmed on a guarantee card attached to this manual. Boiler
should be connected according to producer recommendations, in accordance with this manual.
ATTENTION!
It is recommended to perform the first start-up of the boiler in accordance with the
guidelines included in the Operation and Technical Documentation by a person holding a
valid license (information about persons authorised to start up the boiler is available from
the Producer - phone: +48 85 711 94 56).
ATTENTION!
The return water temperature from the system to the central heating boiler should not be
lower than 45ºC
.