Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 42

42 

 

controlling the sensor. The regulator switches 
off the fan. 

16

 

 ADDITIONAL FUNCTIONS 

16.1

 

Power supply decay 

In  the  cases  of  power  supply  failure,  the 
regulator  will  resume  the  operation  mode  in 
which it was before the failure. 

16.2

 

Anti-freezing protection 

If  the  boiler  temperature  drops  below  5

C, 

the  CH  pump  will  be  enabled,  thus  forcing 
circulation of the boiler water. This will delay 
the process of water freezing, yet in the case 
of great frost or shortage of power, it will not 
protect the system against freezing. 

 

Note:  This  function  must  not  be 
the  only  anti-freezing  protective 
measure!  Apply  other  methods 
too.  Regulator  manufacturer  is 
not 

liable 

for 

anti-freezing 

related damages. 

 

16.3

 

Function of protecting pumps 
against stagnation 

The regulator performs the function of boiler, 
HUW and mixer pumps and servo protection 
from  locking  caused  by  scale  deposit.  To  do 
this,  these  components  are  periodically 
(every 167h) switched on for few seconds. In 
this  way  the  pumps  are  protected  from 
immobilization  caused  by  scale  deposits. 
Therefore,  during  boiler  shut-down,  power 
supply to the regulator should be on, and the 
regulator should be in STANSTILL mode.  

16.4

 

Feeder bunker 

After  connect  an  additional  module  B 
controller  can  be  used  with  the  sensor  low 
fuel  level  in  the  tank  (the  fuel  supply  from 
the  bunker).  Upon  activation  of  the  sensor 
(opening)  at  the  Additional  feeder  operation 
time
  controller  activates  additional  feeder  in 
order to supplement the base fuel tank. This 
parameter can be found in:  
Service settings 

 Burner settings 

If  the  parameter  Additional  feeder  operation 
time
 is set to “0” this work additional feeder 
is turns off. 
 
 

17

 

REPLACEMENT OF PARTS AND 
COMPONENTS  

17.1

 

Replacement of mains fuse  

Mains fuse is located in the Operating Unit. It 
protects  the  regulator  and  other  equipment.  
In case of replacement, use 6.3A.  
In  order to take out the fuse, raise the  fuse 
holder  using  flat-blade  screwdriver  and  take 
out the fuse. 

17.2

 

Replacement of control panel 

It  is  not  recommended  to  replace  only  the 
control  panel  as  the  software  in  the  panel 
must be compatible with the software in the 
rest of the regulator 

17.3

 

Lambda sensor 

Burner  efficiency  can  be  increased  by 
connecting 

additional 

Lambda 

sensor 

module.  Connect  the  module  according  to 
electric  scheme.  Lambda  sensor  is  to  be 
activated in:  
Service  settings 

  Burner  settings 

 

Lambda sensor 
If  parameter  Operation  with  Lambda  sensor 
is  set  on  ON  then  the  controller  will  operate 
using  Lambda  sensor  readings.  The  amount 
of  air  provided  to  the  furnace  will  be 
automatically  set  in  such  a  way  to  obtain 
preset  amount  of  air  in  fumes.  If  this 
parameter is set on OFF then Lambda sensor 
readings  will  not  have  influence  on 
controller’s  operation.  Amounts  of  air  for 
given burner power are set in: 
Boiler settings 

 Output modulation 

Periodical  calibration  of  Lambda  sensor 
readings  can  be  necessary.  To  conduct 
Lambda  sensor  calibration  it  is  necessary  to 
extinguish  the  boiler.  To  make  a  successful 
calibration  the  furnace  in  boiler  must  be 
completely  extinguished.  To  start  up  the 
calibration use the parameter: 
Boiler settings 

 Lambda calibration 

Calibration  process  lasts  approximately  8 
minutes. 
 

 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: