Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 38

38 

 

  Floor On 

It  is  being  used  when  the  mixer  circuit  is  loading  floor  heating 
installation.  The  maximum  mixer  circuit  temperature  is  limited  to  the 
value of max. mixer set temperature. 
Attention:  after  choosing  the  option 

–  FLOOR  switched  on  the 

parameter of max. mixer set temperature should be so edited, that the 
floor  heating  will  be  not  damaged  and  there  would  be  no  danger  of 
scalding.  

  Pump only 

By  the  moment  when  the  mixer  circuit  temperature  exceeds  the  set 
temperature in the parameter mixer set temperature, the mixer pump 
supply  will  be  shut  down.  When  the  circuit  temperature  will  drop  by 
2˚C then the pump will again be switched on. This option is usually be 
used for control of floor heating pump in situation, when this pump is 
operating together with thermostatic valve without actuator.  

Thermostat select 

Options to choose from: 
Off:  (it  cuts  the  influence  of  room  thermostat  upon  the  boiler 
operation.) 
Universal:  (it  turns  on  the  NO-NC  room  thermostat  coupled  to  42-43 
contacts, it is required to use thermostats with 1K hysteresis.) 
ecoSTER:  (this  option  is  available  after  remote  control  device 
ecoSTER TOUCH is being connected, thermostat signal is being send 
from room panel.) 

Min. mixer temperature 

It is the parameter used for limitation of choosing too low value of set 
mixer  circuit  temperature  by  the  user.  Automatic  regulation  (e.g. 
periodic  temperature  reduction)  also  does  not  cause  the  reduction  of 
set temperature value below the value given in this parameter. 

Max. mixer temperature 

This parameter has two functions: 
_  it  enables  the  limitation  of  choosing  too  high  value  of  set  mixer 
temperature  by  the  user.  Automatic  regulation  (correction  upon 
heating  curve,  that  comes  from  outside  temperature)  also  does  not 
cause  crossing  the  set  temperature  above  the  value  given  for  this 
parameter.  
_  when  the

 

Mixer  support  = On

then  the  mixer  pump  will  shut  down 

by  max.  mixer  temperat

ure  +5˚C,  which  protects  the  floor  against 

destruction. For the floor heating it should be set for the value below 
45+/-

50 ˚C or even lower, when the thermal resistance of this floor is 

lower. Attention: setting too lower value of this parameter can lead to 
unnecessary shut down of the pump.

  

 

Proportionality range 

This parameter affects the movement of the mixer actuator. Increasing 
this  value  results  in  the  mixer  reaching  the  set  temperature  faster. 
Setting this parameter to excessive values causes deregulation of the 
temperature and unnecessary actuator movement. The proper values 
is  set  experimentally.  It  is  recommended  to  set  this  parameter  in  the 
range of 2-6 [3]. 

Integration time constant 

The  greater  the  value  of  this  parameter,  the  slower  is  the  actuator 
reaction  for  temperature  deviation.  Setting  too  lower  values  can  lead 
to  unnecessary  actuator  movements,  too  high  value  extending  the 
time  needed  to  find  set  value  of  the  temperature.  The  right  value  is 
being  edited  according  to  research  results.  It  is  recommended  to  set 
this parameter value between 100 and 180 [160]. 

Valve opening time 

The  time  of  valve  full  opening  should  be  entered 

–  this  time  can  be 

read from the nameplate of valve actuator, e.g. 140s. 

Pump Off by thermostat 

Setting  this  parame

ter  to  “YES”  results  in  closing  the  mixer  and 

deactivating  the  mixer  pump  after  opening  the  room  thermostat 
contact (the room is warm). This setting is not recommended because 
the heated room may cool down too much. 

Mixer input dead zone 

This  parameter  determines  the  value  of  temperature  insensitivity 
(dead  zone)  of  the  mixer  control  system.  The  regulator  controls  the 
mixer so that the measured temperature in the mixer circuit sensor is 
equal  to  the  set  temperature.  In  order  to  avoid  frequent  actuator 
movements  which  can  wear  it  down  unnecessarily,  the  parameter 
should only be regulated when the measured temperature of the mixer 
circuit  is  lower  or  higher  than  the  set  temperature  by  a  value 
exceeding the 

Mixer input dead zone

14.6

 

OTHER PARAMETRES 

 

Show advanced setup 

Available options: 
YES (shows hidden parameters, which edition is not recommended) 
NO (hides hidden parameters). 

Restore default settings 

Restoring the service settings will automatically lead to restoring the 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...