6
7 VG9H 70 en
Electronics (output)
Usage:
Position transmitter (T) /
device status output (S)
Electrical connections: 0.25–2.5 mm
2
Output signal:
Defined by type code option T or S
T: 4–20 mA = 0–100 % position
S: 4 mA = OK
5 mA = Pneumatics test
6 mA = PST test
7 mA = ETT test
8 mA = Warning
10 mA = Alarm
12 mA = Safety position requested
by LCP
Fault modes indicated by levels 3.5
and 22 mA
Galvanic isolation; 600 V DC
Supply voltage:
12–30 V
Resolution:
16 bit / 0.244 μA
Linearity:
<0.05 % FS
Temperature effect: <0.35 % FS
External load:
max 0–780 Ω
LCP9H interface
Electrical connections: 0.25–2.5 mm
2
Local user interface functions
Monitoring of valve position, temperature, supply
pressure, actuator pressure difference, housing pres-
sure, input signal and safety signal status
Guided start-up function
LUI may be locked remotely to prevent unauthorised
access
Calibration
Parameter selection
Testing
Language selection
Alarm and warning state indications
Latest event view
See Chapter 4 for details of LUI functions.
NOTE:
See chapter 8.1.3.5 for SIL certified position transmitter
(T01) details. See Safety Manual for functional safety infor-
mation.