![MessKonzept FTC400 Operating Manual Download Page 37](http://html.mh-extra.com/html/messkonzept/ftc400/ftc400_operating-manual_1775515037.webp)
Page 36 of 49
“Analog Out 1“ is a non DC-isolated 0 to 10V output. The maximum load is 1kOhm. The following
parameters can be routed to “AOut-Parameter “:
Value
Param. No.
Param. Name
Descriptions
0
-
-
No output
1
P0
Compound ppm
Measuring signal in ppm
2
P1
Compound raw
Linearized raw signal in ppm
3
P2
Norm. signal
Normalized measuring signal
4
P3
TC average
Thermal Conductivity in mV
5
P53
Block Temp
Block Temperature
6
P133
Aux ppm
Linearized and calibrated signal in ppm
7
P134
Aux norm.
Normalized signal
8
P67
IOut
Current Loop
“AOut1-Offset“ and “AOut-Gai“ allow to scale the analog output according to a linear equation
(Output= AOut1-Gain
·
AOut1Offset).
File name: Manual_FTC400_1.09KD181129CWI1V01.pdf