Page 35 of 49
• “I/O Mode, 0-20mA (Err)“ This mode works in the analogous manner as the previously
described mode. In case of an error the current output is set to the value specified in the
submenu “I-Out Error“.
• “I/O Mode, 0-20mA (Corr.)“ The current output of this mode creates a voltage drop from 0V
to 10V at a 510 Ohm resistor. (Correction factor: Parameter 73)
• “Const. I-Out“ The output of the current loop is constant current specified in the submenu
“I-Out Const“. Set the value to 0.0mA if the current loop is not used.
The current specified for signalling errors should be outside the measuring range. By default the
error current is set to 3.0mA, values up to 22.0mA can be set. When choosing the “Cal. active“
option the currently measured value is shown at the current output during the calibration. When
choosing the “Cal. frozen“ the last measured value before the calibration began is shown at the
current output.
8.3.2
Analog Output 1
File name: Manual_FTC400_1.09KD181129CWI1V01.pdf