List of addresses and description
Address*
[ factory preset ]
description
options
0
– without filtration
1
– 1,5 sec filter
2
– 2 sec filter
3
– 2,5 sec filter
4
– 4,5 sec filter
5
– 7 sec filter
6
– 10,5 sec filter
A_00
[ 0 ]
Input signal
filtering settings
****
7
– 20 sec filter
0
– 0 to 20 mA
1
– 4 to 20 mA
2
– 0 to 10 V
3
– potenciometer 0 to 100%
4
– user def. current input I
5
– user def. voltage input U
6
– low v/- 585 mV
A_01
[ 1 ]
Input signal
selection
7
– user def. potenciometer
A_02
[ 0.00 ]
Starting point
of the scale
+/- 60000 digits
A_03
[ 200.00 ]
End point
of the scale
+/- 60000 digits
A_05
[ XXXX
.
XX ]
Decimal point
allowed positions are indicated, last position = dec. point off
00
.
0
.
0
.
0
.
0
.
0
– 25% brightness
1
– 50% brightness
2
– 75% brightness
A_06
[ 2 ]
Display
brightness
display brightnes is changed immidiatelly, setting is saved after
the key is pressed.
3
– 100% brightness
A_08
[ 0.00 ]
User input scale start point
It is necessary to have a signal source representing the start point connected to
the input during settings
+/- 60000 digits
A_09
[ 20.00 ]
User input scale end point
It is necessary to have a signal source representing the end point connected to
the input during settings
+/- 60000 digits