Digital process meter DMP 11 provides physical value measuring with
displaying it within -60000 to +60000 digits range. Internal analogue
sigma-delta converter offers resolution of one digit even in full scale
range. Device provides adjustable input signal scale, output signal
scale, decimal point and etc. to fit any kind of application. User can even
set his own calibration for current, voltage (low, high) and potencimeters
signals. Potencimeter measuring is based on the ratio measurement,
slow changes in total potentiometer resistance do not affect
measurement accuracy. Device has implemented NAMUR NE43 input
current loop 4-20mA checking, with defined behaviour in case of current
loop error.
FUNCTIONS
DISPLAYS
measured physical value
INPUT SIGNAL SELECTION
by user
SCALE RANGE
upto -60000 to +60000 digits
EXCITATION POWER SUPPLY
included
4 RELAYS FUNCTION
direct / inverse level mode – relays closes / opens when limit is
reached
direct window mode – relays closes in range defned by numeral
hysteresis and limit value
inverse window mode – relays closes when signal is out of range
defined by numeral hysteresis and limit value
NUMERAL HYSTERESIS
for each limit
TIME HYSTERESIS
for each limit
ANALOGUE OUTPUT
fully adjustable by user
0 / 4 – 20 mA DC, 0 – 10 V DC
inverse AO : 20 – 4 / 0 mA , 10 – 0 V DC
fully adjustable eg. 12-18 mA , 1,6 – 8,3 V
TARA and
HOLD FUNCTION
as standart equipment
DIGITAL INPUT
for TARA and HOLD function (optional acc.)
INPUT 4-20 mA CURRENT LOOP CHECK
comply to NAMUR NE43 *
defined relays and analogue output behavior
DISPLAY BRIGHTNESS
in 4 levels
LIMIT L1 VALUE RANGE RESTRICTION
for operating
personnel
DIGITAL FILTERS
for measured signal
GALVANIC INSULATION
Power supply from: input, output, excitation power supply & relays
input signal from output signal
relays output betweeneach other
*) valid signal is within range 3,8 mA to 20,5 mA
**) 130mA excitation power supply is an optional accessory
***) DMP11-10010 version only
****) DMP11-22121 version has max. operating temp 45°C
DIGITAL PROCESS METER DMP 11
230 V or 24 V power supply
for current and voltage signals
TECHNICAL DATA
DISPLAY
-60 000 to +60 000 – red LED 14,2 mm
PWR.SUPPLY 230V
230 VAC (-20% / +15%)
24 VAC or 24 VDC (-15% / +20%)
21,6 to 52,8 VDC –
with all accessories
POWER SUPPLY
24V
10,6 VDC to 52,8 VDC
–
without accessories ***
2,5 W – without accessories
+ 0,7 W – 2 relays
+ 1,4 W – 4 relays
+ 0,7 W – isolated analogue output
CONSUPTION
Device has
T500mA fuse
+ 1,0 W / 3.0 W – excitation power supply
Exc. power supply
21,6V @ 30mA or 21,6V @ 130mA **
current input – 50Ω + 13 Ω PTC
voltage input 10 V – 370kΩ
INPUT
RESITANCE
voltage input 295 mV – greater than 10 MΩ
POTENCIOMETER
3-wires connection
(input resistance greater than 1MΩ)
SAMPLES
16,7 meas/sec (internal) ; 4 samples/sec – (display)
DIG.RESOLUTION analogue input – 20 bits / analogue output – 14 bits
RESPONSE TIME
10% to 90% – input / output :
180 ms
(w/out filters)
ACCURACY
+/- 0,1 % from full range +/- 2digits
TEMP.COEFFIC.
0,005 % from full range / °C @ T
ref
= 23°C
ISOLATION
STRENGTH -
230 V
3 kV
power supply vs.input/output/relay
1 kV
input vs.output. vs. digital input
ISOLATION
STRENGTH -
24 V
1,5 kV
power supply vs.input/output/relay
1 kV
input vs.output. vs. digital input
ANALOG.OUTPUT max. 21,5 mA or max. 10,5 V DC
OUTPUT IMPEDANCE
current
: max. 600
Ω |
voltage
: min. 5 kΩ
MAX. OUTPUT
OVERLOAD
current: unlimited
( short-circuit resistant )
voltage : unlimited
( short-circuit resistant )
RELAYS OUPTUT 2 or 4 switching contacts 230 VAC @ 5A
LIMITS L1 – L4
adjustable in full range of scale ( +/- 60 000 )
value –adjustable in range 0 to 30 000
LIMITS L1 – L4
HYSTERESIS
timing – adjustable in range 0,0 to 299,9 sec
level mode – direct / inverse
LIMITS L1 – L4
LOGIC FUNCTION window mode – direct / inverse
DIMENSIONS
96 x 48 x 85 mm (w x h x d) –
cutout 91 x 44 mm
(w x h)
ENCLOSURE
IP40
WIRRING CONNECTION
terminal strip
max. conductor cross-section is 2,5mm
WEIGHT
270 g –
with all accessories
STABILISATION
5 minutes
OPERATING TEMP.
-25 °C to +50 °C ****
STORAGE TEMP.
-40 °C to +85 °C
HUMIDITY
20% < rH < 80% (without consdesation)
OPERATION
continous
SITE ALTITUDE
max. 2000 above sea level
APPLICATION
intended solely for industrial or professional use
EMC compatibility
ČSN EN 61326-1 ed.2 : 2013
EMC radiation
ČSN EN 55011 ed.3 : 2010 + A1:2011,class.B grp.1
ELECTRICAL SAFETY
ČSN EN 61010-1 ed. 2 : 2011,ČSN EN 61010-2-030:2011
EMC immunity influence
max. +/- 0,1% from full signal with unshielded wires
OPTIONAL ACCESSORIES
2 or 4 releays outputs
230 VAC @ 5A
relay output
L1, L2, L3 a L4
Independent. set
Isolated analogue output
0 – 20 mA DC
4 – 20 mA DC
CURRENT
due wirrings
active / passive
VOLTAGE
0 – 10 V DC
Excitation power supply
upto 21,6 VDC @ 130mA +/- 10%
INTRODUCTION
INPUT SIGNALS
Preset
0 – 20 mA DC
CURRENT
4 – 20 mA DC
VOLTAGE
0 – 10 V DC
POTENCIOMETER
0 – 100 %
Adjustable by user
CURRENT
- 4 – 21 mA DC
+/- 0 – 10,5 V DC
VOLTAGE
+/- 0 – 295 mV DC
POTENCIOMETER
100 Ω – 2.0 kΩ