MERAWEX ZUP-230V User Manual Download Page 24

User manual   ZSP121N-DR

             

Nr dok. 0696.00.95-02.0                                       Strona 

8/8 

Appendix 

 
LED signalization, outside the power supply.

 

MAINS 

green LEDdiode 

Reaction 
time 

- no mains, battery disconnected (no-voltage condition)  

- mains on, rectifier operational   

0/1 pulsowanie 

- battery operation (no mains or rectifier faulty)  

FAULT 

yellow LED diode 

 

- no faults 

 

- battery operation (no mains power supply or rectifier faulty) 
- no battery, or the battery has voltage lower than 10V - LVDD remains off 
- battery disconnected or battery fuse blown out [**] 
- decrease of output voltage of power supply down to level lower than 90% of 
floating voltage. **) 
- battery voltage below 22V **) 
- mains voltage below 175V 
- battery circuit resistance too high [*] 
- output fuse blown 
- fuse in additional outputs module (if attached) blown 



90s 
1min 


12min 

0/1 flashing 

- external alarm or internal alarm (open cabinet doors, tamper) *) 

0/1 blinking 

- recognized battery (U> 10V) but has too low voltage (U <21.6V) - RGR remains 
switched off   

*) Alarms are not distinguished 
**) Fast voltage drop when overloading the power supply activates the 22V signalization. Slow lowering starts the 
90% signalization (after 1 minute from exceeding the threshold). When the battery is being charged, the alarm is 
cleared after exceeding the 22V threshold. 
 
Reaction time: 
 

– immediate reaction; 

 

– the selected rows describe permanent states of operation preceding the start of the power supply. 

 

LED signalization inside power supply (PCB packet)  

MAINS 

green LED 

Reaction 
time 

- no mains

 

- mains on, rectifier operational 

0/1 blinks 

- mains on, damaged rectifier 

BAT 

yellow LED 

 

- battery correct [**] 

- high resistance of battery circuit [*] 

12min 

0/1 
pulsowanie 

- no battery or battery fuse blown 

90s 

[*]  The measurement is performed every 10 minutes. The first detected overrun activates the signalization on the 

BAT

 PCB packet and reduces this time down to 1m. After detection of the next two exceedances, the 

FAULT

 

external signalization is activated. Thus, the maximum detection time of the exceedance is 12 minutes. The first 
correct measurement cancels the signal. 
[**] When the battery fuse is faulty or the battery has been disconnected, the LVDD is automatically switched off 
due to the voltage drop below its level. Reconnecting the battery or replacing the fuse results in the LVDD being 
switched on without delay. 
 

Relay signalization 

MAINS FLT 

Mains fault 

Reaction 
time *) 

- no mains (only mains, does not react to rectifier fault)  

 

- mains on 

 

GEN FLT 

General fault 

 

- whenever 

FAULT

 LED is on, flashes or blinks   

 

- no faults 

 

–de-energized relay

 

–energized relay

 

 
*)   The 

MAINS FLT

 and 

GEN FLT

 relays react to the power failure and its return with delay of 6s. 

 

The 

GEN FLT

 relay immediately follows the 

FAULT

 signalization. 

Summary of Contents for ZUP-230V

Page 1: ...OWER SUPPLY ZUP 230V The document contains USER MANUAL Power supply for fire alarm devices heat and smoke control systems fire protection and fire automation systems ZUP 230V 400 ZUP 230V 700 ZUP 230V...

Page 2: ...f admittance CNBOP No 3183 2018 14 May 2018 Technical description 2 1 1 Application 2 1 2 Technical data 3 Construction 4 Functioning of outputs 6 Description of 230Vac distribution packet of ZUP powe...

Page 3: ...while waiting for a fire alarm This allows to extend the supervision time to 72h while maintaining the readiness to operate powered devices with full power depending on the type 400 1500W The power su...

Page 4: ...bottom ZUP 230V 8 Dimensions and weight A B C D E F G Weight with battery ZUP 230V 400 700 1000 455 406 207 438 310 360 410 42 kg 45Ah ZUP 230V 1500 555 456 207 488 410 410 470 65 kg 75Ah Fig 1 Dimens...

Page 5: ...A Environmental class EN 12101 10 2007 class 1 Radio disturbances EN 55022 2013 class B EMC immunity EN 50130 4 2012 A1 2015 EMC emission EN 61000 3 2 2007 A1 2010 A2 2010 EN 61000 3 3 2011 Construct...

Page 6: ...ime it takes to switch from the mains to the battery operation mode Its starting and backup operation takes place from the ZSP121N DR power supply output Then the ZINW 1 connector and the correspondin...

Page 7: ...tage for some time e g aeration gate drive activated by a separate fire alarm signal but it requires 230V power to operate shunt trips of fire protection circuit breaker it is activated manually with...

Page 8: ...ins is present The voltage on this output is maintained for a certain period of time T2 T3 see the description of the times of the AC 1 output so that the actuator can change its state The response to...

Page 9: ...utput about 150ms Outputs AC 4A and AC 4B The AC 4 output is intended for devices that should start operating with some delay after a fire alarm e g smoke exhaust fan which can be activated only after...

Page 10: ...l contact connector of the PE mains unused ZAS ZSP 230V Additional 230Vac mains output unused PROG UP programming connector do not connect G201 Digital communication connector do not connect WYUSZ Fau...

Page 11: ...ashing line fault of fire alarm input from the CSP detected T2 T3 T2 and T3 countdown start signalization yellow LED it is possible to finish countdown of these times faster by means of TEST button Co...

Page 12: ...the HDGs type 1 5mm2 is recommended For devices made in the 2nd class of insulation it is possible to use 2 wire cables without using the connection with the PE bus bar Several loads can be connected...

Page 13: ...cannot differ by more than 10 for the binary input the short circuit resistance cannot be higher than 1k and the leakage resistance between lines must not be lower than 100k If these values are exceed...

Page 14: ...th the battery connected and the mains on should result in appearing the voltage on the AC 1 output After power failure the voltage should be maintained for the time T1 Starting the PSU from the batte...

Page 15: ...s of the power supply Time T1 maximum battery life after power failure from 1min up to 8h Setting sum of individual settings 1 2 5 10 30min and 1 2 5h Example in picture 1 5 10 min 1 2 h 3h and 16min...

Page 16: ...nt of the waste This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time but must be returned to the collection point for wast...

Page 17: ...description near the connector Do not obstruct the ventilation Provide at least free space of at least 10cm on the sides of the device allowing the proper ventilation Otherwise the device may be damag...

Page 18: ...limitation Correct end of bulk charging 2h from moment when charging current drops to 90 Immediately after current drops below 25 of charging current Bulk charging emergency termination battery temper...

Page 19: ...lectromagnetic compatibility EN 50130 4 A1 Electrical safety Class I acc to EN 60950 1 A1 Mechanical parameters Dimensions body maximum dimension over the TS 35 rail 160 97 46 mm 54 mm 160 53 5 46 12...

Page 20: ...with two maintenance free batteries which should be placed in its immediate vicinity The end of the temperature sensor of the power supply should be inserted between the two batteries which afterward...

Page 21: ...diode of internal signalization yellow BAT 21 LED diode of internal signalization green MAINS Notes For each fault signal outputs there are 3 relay contacts available The description of the relay con...

Page 22: ...he energized state The state of the relay can be tested for example with an ohmmeter applied between the appropriate outputs of its contacts After removing the interruption in the battery circuit the...

Page 23: ...horized access to the interior of the cabinet Opening the cabinet door after opening the lock causes opening the sensor contacts and generating a fault signal flashing of the FAULT LED of the external...

Page 24: ...eshold Reaction time 0 immediate reaction x the selected rows describe permanent states of operation preceding the start of the power supply LED signalization inside power supply PCB packet MAINS gree...

Reviews: