User manual ZUP-230V
Nr dok. 0697.00.95-02.3
14/15
Connecting additional 1k
Ω resistor to CSP
input
+
+
–
+
–
Disconnection of additional 1k
Ω resistor
from CSP
–
+
–
+
–
after time T2+T3
–
+
–
+
+
With the parameterization of the fire alarm input set, its failure activates fault signalization, which
should disappear after connecting a 10k
Ω resistor. In this state, connection of a 1kΩ resistor is
recognized as occurrence of a fire alarm, which results in switching off the voltage from the AC-2A
output. The subsequent disconnection of the 1k
Ω resistor (disabling the fire alarm) should result in the
output on the AC-2A output, but only after the countdown of the time T2+T3.
5.7.3. Setting time
There are two slide switches on the 230Vac voltage distribution packet that allow you to set all
three times to organizing the activation of the AC-1, AC-2, AC-3 and AC-4 outputs of the power
supply.
Time T1
:
- maximum battery life after power failure (from 1min up to 8h)
Setting:
- sum of individual settings: 1, 2, 5, 10, 30min and 1, 2, 5h.
Example in picture: (1+5+10)min + (1+2)h = 3h and 16min
Time T2
:
- maximum time of power supply activity after a fire alarm (from
1min to 6min and from 1 up to 6h)
Setting:
- sum of individual settings: 1, 2, 3 and unit selection: min. or h.
Example in picture: (1+2)min = 3min
Time T3
:
- delay of AC-4 output operation (from 5s up to 65s)
Setting:
- sum of individual settings: 5, 10, 20, 30s
Example in picture: (5+30)s = 35s
The absolute values of the set times depend on the construction and the required way of powering
a specific object.
Factory settings:
T1
: 5min
T2
: 5min
T3
: 5s
Additional information
6.1. Manufacturer's notes
The producer reserves the right to introduce construction and technological changes that do not
impair the quality of the product .
6.2. Proceeding with packaging, used products and batteries
T1: h
1
2
5
30
10
5
2
1
T1: m in
1 2
5 6
ON
3 4
7 8
T2: m in
1
2
3
h
5
30
20
10
T3: s
1 2
5 6
ON
3 4
7 8