own fuse, the common disconnector enables reliable disconnection of the battery from the entire
power supply.
All connections should be made carefully, remembering that during the battery operation (when no
mains power) the current consumed by the inverter can reach up to 80A.
In order to properly compensate for the temperature of battery floating voltage, the temperature
sensor of the ZSP121N-DR power supply should be placed between the side walls of the both
batteries.
5.6. Connection of alarm input from fire alarm control panel (CSP).
The fire alarm input from the CSP can be set both in the operating mode with parameterization in
which the resistance of the signal line is monitored during both the supervision and alarm time as well
as in the normal binary input operation mode. In both cases, however, it is required that the
parameters of the control circuit be within certain specified limits:
-
for the input with parameterization of the resistance value, taking into account the resistance
of connections and leakage resistance (between the lines) cannot differ by more than 10%;
-
for the binary input, the short-circuit resistance cannot be higher than 1k
Ω and the leakage
resistance (between lines) must not be lower than 100k
Ω.
If these values are exceeded, the power supply signalizes the WYUSZ fault.
Fig.8.
Ways to connect CSP fire alarm input.
5.7. First start.
The designations used in the description come from Fig.2. and Fig.7.:
MAINS
- green LED on the door of the power supply box
FAULT
- yellow LED on the door of the power supply box
PRACA
- green LED on the 230Vac voltage distribution packet
ZINW-1
- yellow LED on the 230Vac voltage distribution packet
ZINW-2
- red LED on the 230Vac voltage distribution packet
AC-1
- 230Vac voltage on the AC-1 output terminals
ALP
- red LED on the 230Vac voltage distribution packet
INW
- green LED on the 230Vac voltage distribution packet
AC-2A
- 230Vac voltage on the AC-2A output terminals
Symbols used in the tables:
+
- LED on, voltage present at AC-1 output
-
- LED off, no voltage at the AC-1 output
+/-
- LED flashing
+/
––
- LED blinking
5.7.1. Starting power supply.
Notes:
•
connect voltage indicator or load (bulb, motor, etc.) to the AC-1 output;
WYUSZ
CSP
ZAS
ZUP
Fire alarm
ALARM CSP
10
k
1
k
input
CSP PARAM
ON
Switch
WYUSZ
CSP
ZAS
ZUP
ALARM CSP
CSP PARAM
OFF
Operation mode with parameterization
Simple binary input mode
Fire alarm
input
Switch