15
FLUE VENTING
The E-FV33i Insert must be vented vertically to the outside and must use the Mendota Co-Linear flexible ducting system.
The minimum vertical vent length required is 10 feet. The maximum allowed vertical vent length is 70 feet. In the USA,
the air-intake pipe may be run past the damper into the chimney and terminated with an open end 2 feet past the dam-
per mechanism.
NOTE: THE INSERT IS DESIGNED, TESTED AND LISTED FOR OPERATION ONLY WITH MENDOTA
INSERT VENTING COMPONENTS AS LISTED IN FIGURES BELOW:
The solid-fuel fireplace chimney must be clean and in good working order and is constructed on non-combustible
materials
Chimney cleanouts must fit properly.
The refractory, glass doors, screen, and log grates can be removed from the solid-fuel fireplace to accommodate the
gas insert.
Smoke shelves, shields, and baffles can be removed if attached with mechanical fasteners.
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically
approved with this appliance may result in property damage or personal injury.
Cutting of any sheet metal parts on the solid-fuel fireplace is prohibited.
f i r e - p a r t s . c o m