VERTICAL RISE HORIZONTAL TERMINATION 

The minimum vertical section required to be connected directly to the starter adapter on this fireplace is 48 inches when 
used with a maximum horizontal run of 32 ft.  If the total length of the vertical sections connected directly to the starter 
adapter on this fireplace is between 4 feet and 41 feet, you are allowed a maximum 32 feet horizontal run. For other vent-
ing configurations within these maximum limits, see Figure 15, Zone A and Zone B. 

Combined total length of all pipe sections (include restriction of elbows) in the vent system shall be less than 42 feet. 

NOTE:  

The horizontal run of vent pipe must be level or have a ¼" rise for every 1' of run toward the termination.  Never 

allow the vent to run downward.  This will cause high temperatures and the possibility of a fire. 

This ML47 Fireplace must be installed by a qualified Mendota service person 

Position fireplace in desired location.  See Figure 13 for guidelines on proper vent cap placement on exterior of home.  
Check to determine if wall studs are in the way when vent system is attached.  If this is the case you may want to adjust 
the fireplace location. 

Locate where vent pipe will pass through any ceilings and will penetrate the outside wall.  Since vent pipe sections "over-
lap" we suggest pre-assembling and measuring the total vent pipe run so you can more accurately locate the point where 
the vent pipe will penetrate the outside wall (See Figure 13). Be sure all vent components are properly twist locked and 
leak-proof.  Be sure 1000

º

 sealant is used in the inner pipe joints of all pipe sections manufactured by Simpson DuraVent. 

Cut and frame a 10-3/4” wide x 10-3/4”” high opening in the outside wall openings and 10” x 10” opening in ceiling open-
ings.  The outside wall hole must be positioned so the vent system will run level or have a ¼" on rise AND be perpendicu-
lar to the wall.  The height of the opening must be located to meet all building codes and not allow the termination to be 
easily blocked or obstructed.  A ceiling fire stop spacer is required at any floor (ceiling) opening. 
 
Connect vent pipe to the fireplace adapter on top of fireplace vent outlet.  
The horizontal pipe must end flush with the exterior wall of the home.  Horizontal pipe will require a proper support every 3 
ft. of vent pipe.  THERE MUST BE A MINIMUM OF 1" CLEARANCE TO COMBUSTIBLES FROM ALL VENT PIECES ON 
THE SIDES AND BOTTOM AND 3" ABOVE HORIZONTAL RUNS). 
A wall thimble must always be used when penetrating combustible wall materials. 

NOTE:  Combustible wall thickness must be 4" to 8" maximum. 
From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the vent 
cap to the wall with screws.  Seal with high quality caulking. 

NOTE:

  Venting terminal (Vent Cap) should not be recessed into wall or siding. 

Figure 13 
 

 

V min 

H max 

18 in. 

6 in. 

24 in. 

6 ft. 

30 in. 

13 ft. 

36 in. 

19 ft. 

42 in. 

25-1/2 ft. 

48 in. 

32 ft. 

4 ft. - 10 ft.  32 ft. 
10 ft. - 40 ft. Varies 

NOTE:

   DO NOT SEPARATE TELESCOPING SECTIONS. 

THEY MUST BE USED AS COMPLETE ASSEMBLIES. 

Summary of Contents for AA-11-02592

Page 1: ...e department Installation and service must be performed by a qualified installer service agency or the gas sup plier WARNING Do NOT use this appliance if any part has been under water Immediately call...

Page 2: ...appareil et remplacer toute partie du syst me de contr le et toute commande qui ont t plong s dans l lau In the Commonwealth of Massachusetts Installation must be performed by a licensed plumber or g...

Page 3: ...staller une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le in stallez une barri re de s curit cette mesure emp chera les tout petits les jeune...

Page 4: ...20 RAISED HEIGHT INSTALLATION OF ML47 21 How to determine the proper installed height of this fireplace 22 INSTALLATION OF FLAT PANEL TV ON TOP OF ML47 23 ENAMEL PANORAMIC LINER AND FLOOR PLATE INSTA...

Page 5: ...ENTS 45 LOCATION OF MASTER SWITCH AND SYNC SWITCH 46 Remote Control Transmitter Functions 47 REMOTE TRANSMITTER OPERATING INSTRUCTIONS 48 FIRST TIME PILOT LIGHTING INSTRUCTIONS 50 IPI STANDING PILOT S...

Page 6: ...e Building Code A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust v...

Page 7: ...SIONS OVERALL APPLIANCE DIMENSIONS AND FEATURES Removable Cover Plate for Plumbing Electrical Access before unit is placed inside framed cavity Replace Lower Cover Plate before sliding unit into frame...

Page 8: ...em 120VAC 2 Amps Dedicated Hot Power only No switches Fan Speed Controls or Light Dimmers are allowed in the same AC supply circuit Optional fans are controlled using re mote control ACCENT LIGHT SYST...

Page 9: ...T TO FLOOR 0in 0mm GLASS EDGE TO ADJACENT SIDEWALL 16in 406 mm UNIT TO ENCLOSURE SIDEWALL 1 2in 13mm VENT PIPE TOP TO COMBUSTIBLES 3in 76mm UNIT TO ENCLOSURE BACK WALL 1 2in 13mm VENT PIPE SIDES TO CO...

Page 10: ...be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control compart ments burners and circulating air passageways of the appliance be kept clean...

Page 11: ...N INFORMATION Prior to installing at altitudes higher than 7500 please contact the Mendota technical service department for specific venting requirements and venting restrictions MINIMUM ROUGH FRAMING...

Page 12: ...distance up from the Floor Level of this Fireplace If you prefer to take measurements from the Top of the Convection Air Opening note that the Top of the convection air opening is 25 1 16 inches up f...

Page 13: ...more 16 in from of the front surface of the visi ble glass door and if perpendicular to the front surface of the glass door must be located a minimum of 16 from the side edge of the visible glass doo...

Page 14: ...nd ceiling fan are desired Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to adjacent side walls Figure 2 Planning Instal...

Page 15: ...e to prevent cold air drafting problems The chase should not break the outside building envelope in any manner Wall ceiling base plate and cantilever floor of the chase should be insulated Vapor and a...

Page 16: ...ition the finishing mate rial s edges adjacent to the top sides and bottom convection air gap around the glass frame Use the Inner Guide if you installing only the Traditions or Willowbrook Front or i...

Page 17: ...ace s rectangle profile must extend out from the face surface of this fireplace 1 inch if the 19 1 2 framing depth is used and the Inner or Outer Finishing Guides are utlizied A MAXIMUM THICKNESS OF 2...

Page 18: ...p to 1 maximum The Traditions Front can be close to the glass frame or away from the glass frame This front comes with a screen and is a conforming safety barrier For the Traditions Front use the inne...

Page 19: ...e Framing Brackets With Final Finishing Material mounted behind the Grace by using the inner guides the Grace can be mounted only as close as the Final Finishing Ma terial thickness allows This front...

Page 20: ...k as allowed by the Final Finish Material thickness Mount the Traditions or Willow brook Front at the desired depth relative to the Grace Front Note that the Traditions or Willowbrook Front s visible...

Page 21: ...ce from Floor to ML47 Bottom Surface DIM A MAXIMUM Distance from Floor to ML47 Visible Glass Bot tom Edge DIM B LIMITATIONS MUST BE ADHERED TO 84 15 24 3 16 LIMITED by Clearance to Soffit Use metal sh...

Page 22: ...e of the visible glass will be located 9 3 16 up from the floor level in this configuration Mendota recommends that the ML47 be installed on an elevated wood framed support stand of at least 15 tall w...

Page 23: ...bottom edge of the TV cavity as much as possible beyond the 18 minimum requirement Higher up means a cooler TV You MUST create a recessed 5 deep cav ity to house the TV NEVER mount any TV above this f...

Page 24: ...r Mocha Metallic and Silver Metallic attractive colors You must select one col ored Panoramic Panel Kit and install it before any test firing of this appliance The specific color kits and its correspo...

Page 25: ...mounting height of this single gang box with the height of other AC outlets that are installed in the same room as this appliance WARNING DO NOT STAPLE the 6 DC Power Inlet Harness to the wall studs C...

Page 26: ...stalled at a minimum of 12 above the heat outlet 37 up from the floor level of this fireplace and no more than 8 out from wall at that height Non combustible marble brick stone etc mantels can be inst...

Page 27: ...e correct pipe sizes PIPE LENGTH FEET SCHEDULE 40 PIPE INSIDE DIA TUBING TYPE L OUTSIDE DIA NAT L P NAT L P 0 10 1 2 1 3 cm 3 8 1 0 cm 1 2 1 3 cm 3 8 1 0 cm 10 40 1 2 1 3 cm 1 2 1 3 cm 5 8 1 6 cm 1 2...

Page 28: ...his table GAS PRESSURE REQUIREMENTS NOTE For altitudes above 2 000 feet some variations in air shutter settings may be required Figure 4 Gas Valve Pressure Test Ports Manifold pressure must be taken a...

Page 29: ...the 30 minutes of burn time Write the reading here Final Gas Meter Reading _______________ Calculate the following FINAL GAS METER READING INITIAL GAS METER READING Subtract Initial Gas Meter from Fin...

Page 30: ...prepare the rough opening using framing dimensions Be sure to also prepare opening to allow for co axial vent 2 Check to make certain all venting requirements and locations are being followed 3 This...

Page 31: ...e its own separate vent system Common vent systems are prohibited To assure proper venting performance of this high performance Mendota Direct Vent Fireplace it is critical that all brands of vent pip...

Page 32: ...erminal 18 47 cm min K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance to unventilated soffit 18 min 46 cm min L Clearance above paved side walk or a paved driveway located...

Page 33: ...M DESCRIPTION 1 6 or 7 PIPE DuraVent 6 Amerivent 7 2 12 VENT STACK 3 24 VENT STACK 4 36 VENT STACK 5 48 VENT STACK 6 90 GALVANIZED ELBOW 45 GALVANIZED ELBOW 7 ADJUSTABLE WALL THIMBLE not shown 8 ATTIC...

Page 34: ...is 4 In Zone A 32 feet maximum horizontal run allowed with a 4 feet starter section for NG and 27 feet maximum horizontal for LPG If the starter vertical section is less than 4 feet use the chart and...

Page 35: ...rtical section less than 4 feet the following rules apply a You must use the Master Flue Venting Requirements Chart See Zone A below the 4 vertical run line b A single 90 vertical to horizontal elbow...

Page 36: ...LBOWS VERTICAL TERMINATION VERTICAL RISE DUAL 90 ELBOWS HORIZONTAL TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS HORIZONTAL TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS VERTICAL TERMINATION THREE HORIZONTA...

Page 37: ...10 3 4 high opening in the wall The hole must be positioned so the vent system will run level or have a rise per foot of run AND be per pendicular to the wall The height of the opening must be locate...

Page 38: ...netrate the outside wall See Figure 13 Be sure all vent components are properly twist locked and leak proof Be sure 1000 sealant is used in the inner pipe joints of all pipe sections manufactured by S...

Page 39: ...ft 10 ft 28 ft 10 ft 40 ft Varies V1 min H1 max V2 max H2 max 18 in 6 in 36 1 2 ft 42 ft H1 V2 24 in 6 ft 32 ft 34 ft 42 ft H1 V2 30 in 13 ft 27 1 2 ft 42 ft H1 V2 36 in 19 ft 20 ft 42 ft H1 V2 42 in...

Page 40: ...nts DuraVent only are sealed and are leak proof Maintain 1 airspace clearances to combustibles 2 above horizontal runs Cut a 10 x 10 opening in the roof centered in the small drilled hole placed in th...

Page 41: ...e V1 min H max V2 max 18 in 6 in 38 1 2 ft 24 in 6 ft 34 ft 30 in 13 ft 27 ft 36 in 19 ft 21 ft 42 in 25 1 2 ft 14 1 2 ft 48 in 32 ft 10 ft 4 ft 10 ft 32 ft Varies 10 ft 40 ft Varies Varies Figure 17...

Page 42: ...ws must meet some minimum prerequisites Prerequisite 1 The vent system must terminate vertically using a vertical vent cap Prerequisite 2 There must be a minimum 12 inches of vertical starter section...

Page 43: ...t and right corners of glass frame Identify a rec tangle slot on the bottom right and left corners of firebox opening sides Carefully line up the bottom corner tabs in glass frame bottom corners with...

Page 44: ...Check Off List see above must be completed q Check for gas leaks and gas pressures prior to installing facing materials q Install fresh batteries in remote transmitter Follow Initializing the System...

Page 45: ...nd burner media are positioned properly For Natural Gas applications air shutter shall be 1 8 open For LPG applications start with air shutter open to 3 8 After burner has been properly installed and...

Page 46: ...actuate the two switches The Master Switch must be ON for the pilot flame and burner flames to activate The SYNC switch is to be used initially when mating the remote transmitter with the receiver lo...

Page 47: ...replace will stay functioning until the room temperature increases 1o F above the Set Point Temperature To increase the Set Point Temperature Press the UP button until the desired temperature is displ...

Page 48: ...vel 1 and the Down but ton is pressed all burners will turn OFF If in IPI mode the pilot light will also extinguish If in Standing Pilot Mode the pilot light will remain ON Note If in SMART model the...

Page 49: ...to the room thermostat set point etc When the Transmitter batteries are low a Battery Icon will appear on the LCD display of the Transmitter before all battery power is lost When the batteries are rep...

Page 50: ...the pilot flame is lit and well established close glass door WARNING NEVER IGNITE MAIN BURNERS WITH GLASS DOOR REMOVED OR OPEN Doing so will lead to damage to pilot flame sensor and spark electrode w...

Page 51: ...e door glass Further leaving the fireplace in the Standing Pilot Mode will keep the fireplace body warm and eliminate cold drafts and heat loss to the cold air that is trapped inside the firebox REMOT...

Page 52: ...he pilot light flame Use the IPI mode instead during summer months CLEANING VIEWING GLASS The viewing glass should be cleaned periodically Exterior glass surface may be cleaned with cleaner as desired...

Page 53: ...f necessary C Periodically check to verify that the vent system and vent cap are open and free of blockage D Before re installing glass have qualified service person check the operation of the pilot a...

Page 54: ...r plate remove main burner Locate two access plates on the left and right side of firebox floor See diagrams below Unscrew seven outer screws and lift entire left or right cover plate assem bly which...

Page 55: ...e and the Valve Pressure Regulator This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of...

Page 56: ...ner Orifice Spud The Orifice Spud can be removed and installed using a hex wrench WARNING Make certain to Secure the Brass fitting and flex supply tube attached to the orifice in place using a 1 2 ope...

Page 57: ...or failure to use only parts specifically ap proved with this appliance may result in property damage or personal injury AVERTISSEMENT Risque de dommages ou de blessures si les pi ces ne sont pas inst...

Page 58: ...s recom mended that all gas plumbing joints factory installed and field installed are checked for leaks Figure 19 Pressure Test Port PILOT FLAME AND MAIN BURNER RELATIONSHIP VERIFICATION Prior to comp...

Page 59: ...59 P a g e 1 MIN 1 MIN...

Page 60: ...lied in the Owner s Manual Packet to this same surface Prior to attaching the labels fill in all the information that is requested in these labels For installations from 610 1370 meters 2000 4500 ft t...

Page 61: ...ALVE ASSEMBLY REPLACEMENT PARTS LIST ITEM QTY PART NUMBER DESCRIPTION 1 1 05 04 00062 Pilot Assembly 2 2 65 14 00180 ORIFICE 1 8 3 1 HA 90 00004 Proflame Valve Assembly with fittings 4 1 55 02 00070 T...

Page 62: ...cal Code Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and danger ous operation and Verify proper operation after servicing Attention Au momen...

Page 63: ...y Con tact your dealer for more detailed ordering information Figure 22 GLASS FRAME ASSEMBLY HA 90 00102 REPLACEMENT PARTS LIST ITEM PART NUMBER DESCRIPTION 1 HA 90 00103 FRAME WELDMENT GLASS ML47 2 6...

Page 64: ...ound on the rating plate which is located in the air gap below the glass frame near the center When contacting your dealer for any cleaning service or warranty service always provide the Model Number...

Page 65: ...65 P a g e THIS PAGE LEFT BLANK INTENTIONALLY...

Page 66: ...66 P a g e THIS PAGE LEFT BLANK INTENTIONALLY...

Page 67: ...d and leak proof Check minimum and maximum vertical horizontal and vent runs 1000 sealant must be used on inner joints at adjustable pipe sections q CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES VENT LO...

Page 68: ...68 P a g e TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Page 69: ...ases that have not received prior written approval from Mendota NOTE Minor warping of certain parts or discoloration is normal and is not a defect covered by this warranty Major warping of parts can b...

Page 70: ...70 P a g e Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com 85 03 00923...

Reviews: