INSTALLATION INSTRUCTIONS AND 

USER GUIDE

Part no. 744012EN, Week 47/2019 EN

External wireless CO

2

 sensor  

M-WRG-II FSC

1

2

3

Fig. 1:  External wireless CO

2

 sensor

Item in Fig. 1

Description

1

Control button (touch-sensitive)

2

Status LED

3

Mode LEDs (5x)

Introduction

1.1  Notes on these instructions

These instructions contain important information that 

should be followed when installing and using the wire-

less CO

2

 sensor.

 

► Read all the instructions carefully to avoid possible risks and 

mistakes.

 

► These instructions are part of the product. Keep the instructions 

in a safe place for future reference.

NOTICE

 

► When operating the ventilation unit, also follow the operating 

instructions that were supplied with your unit.

1.2  Description

The wireless CO

2

 sensor is used for wireless operation of ventilation 

units from the M-WRG-II and M-WRG series constructed from 2020 

onwards (excluding bus unit types). It can also be used to determine 

the CO

2

 concentration at an installation location selected by you, 

provided that it is within the wireless range. The “CO

2

 control” and 

“Automatic mode” ventilation programs use the transmitted values 

to automatically adjust the unit’s air flow to the required ventilation 

level. One wireless CO

2

 sensor may be linked to each ventilation 

unit. If the ventilation unit has an internal CO

2

 sensor, it will be auto-

matically disabled. The wireless CO

2

 sensor incorporates the CO

2

 

control function into ventilation units without an internal CO

2

 sensor. 

The control button (item 1 in Fig. 1) is used to activate five different 

ventilation levels/programs. The current selection is indicated by 

one of the five green mode LEDs (item 3 in Fig. 1). The multi-

coloured status LED (item 2 in Fig. 1) signals the wireless sensor 

and ventilation unit operating statuses. If the CO

2

 concentration 

exceeds 800 ppm (factory setting) in the “CO

2

 control” or “Automatic 

mode” ventilation program, the ventilation level is increased contin-

uously up to max. 60 m

3

/h until the CO

2

 concentration in the room 

drops back below 800 ppm. When it is started for the first time, the 

wireless CO

2

 sensor takes 2 minutes to calibrate itself so that it can 

return stable values.

The wireless sensor is fixed to the wall with the dowels and screws 

provided (see section 4.1). A 230 V connection is needed for oper-

ation.

The optional M-WRG-FBH wireless remote control, part no. 5478-10, 

can be used to program the functions of the wireless sensor. You 

will find more details in the “User guide for wireless remote control 

M-WRG-FBH”. The wireless CO

2

 sensor can also be used in parallel 

with the M-WRG-FBH wireless remote control, M-WRG-FT 4-way 

wireless pushbutton switch and M-WRG-II FSF wireless humidity 

sensor and in conjunction with the U

2

 installation version and all 

M-WRG-II and M-WRG covers.

1.3  Target group

These installation and operating instructions are aimed at two target 

groups:

The activities described in chapter “4 Installation and set-up” must 

only be carried out by specialised personnel with the following 

qualifications:

 

— Training in the installation and commissioning of electrical 

devices

 

— Training in electrical hazards and the local safety requirements

 

— Knowledge of the relevant standards and directives

 

— Knowledge and observance of this document and all the safety 

instructions

The other chapters of this document are intended for users of the 

wireless CO

2

 sensor. No special prior knowledge is needed.

1.4  EU declaration of conformity

The wireless CO

2

 sensor described below

  Type: M-WRG-II FSC 

  Part number: 733011

manufactured by

  Meltem Wärmerückgewinnung GmbH & Co. KG 

  Am Hartholz 4 

 

D-82239 Alling

conforms to the regulations and standards listed in the EU Declara-

tion of Conformity.

1.5  Technical data

Product characteristics

Dimensions (W x H x D)

100 mm x 100 mm x 25 mm

Weight

approx. 125 g

Colour

white, similar to RAL 9010

Material of the plastic parts

ABS

Ambient conditions

Ambient temperature during  

operation

0 °C to 40 °C

Ambient temperature for storage and 

shipping

-20 °C to 55 °C

Relative humidity

0 % to 90 %,  

non-condensing

IP code (IEC 60529)

IP30

Electrical connection

Operating voltage

195 V AC to 253 V AC

Mains frequency

50 Hz

Maximum power consumption

4 W

Cable cross-section

0.25 mm

2

 to 2.5 mm

2

Wireless connection

Communication frequency

868.3 MHz

Output power

at least 0 dBm

Data logging

Measurement range

400 ppm to 2,000 ppm

Measurement accuracy (within the 

measurement range, >10 minutes 

after switching on)

40 ppm + 2 % of the  

measured value at 20 °C

Time taken to achieve measurement 

stability after switching on

2 min