P01 - Temperature set point
Move DIP switch S1 located on the side of thermostat to ON position.
“P01” and the temperature set point will appear on display.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: 5…60°F / -15…+15°C, Default: 37°F / 3°C
As long as the ambient temperature is lower than the temperature
set point P01, the PYROTRACE will turn ON.
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROBOX3/3C/5
-TRACE
Owner’s manual & Technician Settings
Pg. 9
Temperature
set point
Technician settings
Use the technician settings mode to view and adjust the following parameters:
P01
Temperature set point
P02
Lower ambient temperature limit to stop
heaters
P03
Time delay before stopping the heaters
P04
ON time for manual mode
P05
Heaters cycle time / Splitting time
P06
Enable/Disable 2
nd
temperature sensor
logic (Aquastat)
P07
Heaters outputs logic
P08
MODBUS MAC Address for home
automation system (option)
P09
Commissioning / Test mode
Restore defaults
Move DIP switch S1 located on the side of thermostat to ON position.
Press the [SELECT] and [+] buttons simultaneously to move forward to the next
technician parameter.
Press the [SELECT] and [-] buttons simultaneously to return to the previous
technician parameter.
Enter technician settings mode
Enter technician
settings mode
Important: Changes made to technician parameters will not take effect as
long as DIP switch S1 is in ON position.
Save changes
and exit
technician
settings mode
Parameters:
Save changes and exit technician settings mode
Move DIP switch S1 located on the side of thermostat to OFF position.